Hart-enabled analog-digital converter module
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

Setting example
Ex.
When 20000 is set for the scaling upper limit value and 4000 is set for the scaling lower limit value for the module with the
input range of 0 to 20mA.
32000
S
H
0
S
L
0
mA: Analog input current (mA)
S
: Scaling upper limit value: 20000
H
S
: Scaling lower limit value: 4000
L
Current input (mA)
0
4
8
12
16
20
Ex.
When 20000 is set for the scaling upper limit value and 4000 is set for the scaling lower limit value for the module with the
input range of 4 to 20mA (extended mode).
32000
S
H
0
S
0 4
L
mA: Analog input current (mA)
S
: Scaling upper limit value: 20000
H
S
: Scaling lower limit value: 4000
L
Current input (mA)
0
4
8
12
16
20
20.3835
1 FUNCTIONS
30
1.6 Scaling Function
mA
20
Digital output value
0
6400
12800
19200
25600
32000
mA
20
Digital output value
-8000
0
8000
16000
24000
32000
32767
Scaling value (Digital operation value)
4000
7200
10400
13600
16800
20000
Scaling value (Digital operation value)
0
4000
8000
12000
16000
20000
20384