7
PARAMETER SETTINGS
7.1
Setting Parameters
1.
Add the FX5-DP-M in the GX Works3. ( Page 95 Create a new project)
[Navigation window] [Parameter] [Module Information] Right-click [Add New Module]
2.
Set the module parameters.
[Navigation window] [Parameter] [Module Information] [FX5-DP-M] [Module Parameter]
3.
Start PROFIBUS Configuration Tool and configure the PROFIBUS module settings. ( Page 50 PROFIBUS Module
Setting)
[Navigation window] [Parameter] [Module Information] [FX5-DP-M] [PROFIBUS Module Setting]
4.
Update the PROFIBUS labels.
[Navigation window] [Parameter] [Module Information] [FX5-DP-M] [PROFIBUS Module Settings]
[PROFIBUS Configurator Tasks] [Setup Tasks] [Update PROFIBUS Label]
5.
Convert some program codes or all program codes.
[Convert] [Convert] or [Rebuild All]
6.
Write the set parameters by the above procedure to the CPU module or the SD memory card in the CPU module with the
GX Works3. ( Page 50 Writing Parameters)
[Online] [Write to PLC]
7.
The settings are applied by powering off and on the system or resetting the CPU module.
7 PARAMETER SETTINGS
48
7.1 Setting Parameters