Profibus-Dpv1; Acyclic Communication Function - Mitsubishi Electric FX5-DP-M User Manual

Melsec iq-f series
Table of Contents

Advertisement

4.3

PROFIBUS-DPV1

The following PROFIBUS-DPV1 functions are available on the FX5-DP-M.
Function

Acyclic communication function

Alarm acquisition function
• To use the PROFIBUS-DPV1 functions, use DP-Slaves that support the PROFIBUS-DPV1.
For details, refer to the following.
Manuals for the DP-Slave
• Use the PROFIBUS-DPV1 functions by setting MSI (Min. slave interval) to a value larger than the bus cycle
time calculated from Pt (Polling time), Tsdi (FX5-DP-M request/response processing time ÷ transmission
speed[bps]), and Lr (Data refresh time). If MSI is smaller than a value calculated from Pt, Tsdi, and Lr,
function processing may take longer than expected. ( Page 164 Bus cycle time)
Acyclic communication function
This function enables reading/writing data from/to DP-Slaves at any time apart from the data exchange.
A maximum of eight requests can be issued.
 Data exchange
 Data reading from a DP-Slave
 Data writing to a DP-Slave
Precautions
The Acyclic communication function cannot execute with the global control function.
4 FUNCTIONS
30
4.3 PROFIBUS-DPV1
FX5-DP-M
Reference
Page 30
Page 32

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents