SPECIFICATIONS
This section describes the specifications of FX5-DP-M.
2.1

General Specifications

General specifications other than the following are the same as the CPU module to be connected.
Refer to the following manual for general specifications.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
Item
Dielectric withstand voltage
Insulation resistance
2.2

Power Supply Specifications

Shows power supply specifications.
Item
Internal power supply
2.3

Performance Specifications

Shows performance specifications of FX5-DP-M.
Item
PROFIBUS-DP station type
Transmis
Electrical standard and characteristics
sion
Medium
specifica
Network configuration
tions
Data link method
Encoding method
Transmission speed
Transmission distance
Max. No. of repeaters (Between DP-Master and
DP-Slave)
No. of connectable modules (per segment)
Max. No. of DP-Slaves
No. of connectable nodes (No. of repeaters)
Transmittable data
No. of occupied I/O points
Applicable CPU module
Applicable engineering tool
No. of connectable units
*1 Transmission speed accuracy is within ±0.2% (compliant with IEC61158-2).
2 SPECIFICATIONS
18
2.1 General Specifications
Specifications
500 V AC for 1 minute
10 MΩ or higher with 500 V DC
insulation resistance tester
Specifications
Power-supply voltage
24 V DC
Current consumption
150 mA
Description
DP-Master (Class 1)
Compliant with EIA-RS485
Shielded twisted pair cable (Page 45 Wiring for PROFIBUS cable)
Bus topology (or tree topology when repeaters are used)
• Between DP-Masters: Token passing
• Between DP-Master and DP-Slave: Polling
NRZ
*1
9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps
Differs depending on the transmission speed. ( Page 19 Transmission distance)
3 repeaters
32 per segment (including repeaters)
64 (Page 40 Configuration of PROFIBUS-DP network)
32, 62(1), 92(2), 122(3), 126(4)
Input data
Max. of 2048 bytes (Max. of 244 bytes per DP-Slave)
Output data
Max. of 2048 bytes (Max. of 244 bytes per DP-Slave)
8 points
FX5U CPU module (Ver.1.110 or later)
FX5UC CPU module (Ver.1.110 or later)
GX Works3 (Ver.1.050C or later )
PROFIBUS Configuration Tool (Ver.1.02C or later)
1 unit
Between all terminals and frame of communication
connector