10.4

List of Error Codes

This section lists the error codes that result from the processing for data exchange between the FX5-DP-M and DP-Slaves or
the processing requests from the CPU module on the own station.
Error codes are classified into major error, moderate error, and minor error.
Error code
LED status
1800H
ERROR on
1801H
ERROR on
1806H
ERROR on
180CH
ERROR on
1810H
ERROR on
1811H
ERROR on
2250H
ERROR on
3C00H
ERROR on
3E07H
ERROR flashing
3E08H
ERROR flashing
3E0BH
ERROR flashing
3E0DH
ERROR flashing
3E0EH
ERROR flashing
3E0FH
ERROR flashing
3E1EH
ERROR flashing
3E1FH
ERROR flashing
3E61H
ERROR flashing
10 TROUBLESHOOTING
116
10.4 List of Error Codes
Error details and cause
A DP-Slave which is duplicated the FDL
address with a DP-Master exists in the
parameter.
Even one DP-Slave is not set for data
exchange.
The parameters have not been written.
The parameters contain a DP-Slave with the I/
O data size set to 0 byte.
The refresh settings are disabled regardless
of the data consistency function is set to
"Enable (Use Autorefresh)".
A hardware failure has been detected.
An extended parameter error has been
detected.
A hardware failure has been detected.
A hardware failure has been detected.
A hardware failure has been detected.
A hardware failure has been detected.
Out of range parameter data are written.
A hardware failure has been detected.
A hardware failure has been detected.
A hardware failure has been detected.
A hardware failure has been detected.
A hardware failure has been detected.
Action
Check the FDL addresses for the DP-Master and DP-Slave and
then configure the parameters with the different FDL addresses.
Check the following items to perform data exchange at least one
DP-Slave.
• Are "Slave is active" of the slave parameters checked?
• Are all the DP-Slaves not switched into reserved stations with the
temporarily reserved station specification function?
Rewrite the parameters.
Check the slave parameters and set the I/O data sizes of each DP-
Slave to 1 byte or more.
The refresh settings need to be enabled when the data consistency
function is set to "Enable (Use Autorefresh)".
Reset the refresh settings and data consistency settings and
rewrite the parameters.
Please consult your local Mitsubishi representative.
• Write the extended parameters to the CPU module.
• Check the extended parameter settings and rewrite the extended
parameters to the CPU module.
• If the error continues to occur after writing the extended
parameters to the CPU module, replace the module.
Take measures to reduce noise, then power off and on the system
or reset the CPU module before running.
If the error occurs again, the possible cause is a hardware failure of
the module, or extension cable. Please consult your local
Mitsubishi representative.
Rewrite the parameters.
If the error recurs, replace the module.
Rewrite the parameters.
If the error recurs, replace the module.
Rewrite the parameters.
If the error recurs, replace the module.
Check and rewrite the parameter.
If the error recurs, please consult your local Mitsubishi
representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.