Set the slave parameters for the PROFIBUS-DPV1 functions.
[Slave User Parameters]  [Next]
Item
DP V1 support enabled
'Fail Safe' function enable
Slave-specific check of cfg_data
Update Alarm
Status Alarm
Manufacturer Specific Alarm
Diagnostic Alarm
8 PROFIBUS Configuration Tool
92
8.3 "PROFIBUS Network" window
Description
Checks this box to use the PROFIBUS-DPV1 function.
• Not checked: The PROFIBUS-DPV1 function is disabled.
• Checked: The PROFIBUS-DPV1 function is enabled.
Checks this box to turn the DP-Slave into the 'Fail Safe' state when the clear request is sent from the DP-Master.
This item can be set when the DP-Slave supports this function.
This item is fixed to "Checked" depending on the DP-Slave used.
For the 'Fail Safe' state setting, refer to the following.
Manual for the DP-Slave
• Not checked: Not turn into the 'Fail Safe' state.
• Checked: Turns into the 'Fail Safe' state.
Check this box when the parameter check method of the DP-Slave is different from that of the standard function of the
PROFIBUS.
This item can be set when the DP-Slave supports this function.
For the parameter check method, refer to the following.
Manual for the DP-Slave
• Not checked: Performs the PROFIBUS standard parameter check.
• Checked: Performs the parameter check specific to the DP-Slave.
Check this box to allow Update Alarm to be sent.
This item can be set when the DP-Slave supports this function.
This item is fixed to "Checked" depending on the DP-Slave used.
• Not checked: Prohibits sending of Update Alarm.
• Checked: Allows sending of Update Alarm.
Check this box to allow Status Alarm to be sent.
This item can be set when the DP-Slave supports this function.
This item is fixed to "Checked" depending on the DP-Slave used.
• Not checked: Prohibits sending of Status Alarm.
• Checked: Allows sending of Status Alarm.
Check this box to allow Manufacturer Specific Alarm to be sent.
This item can be set when the DP-Slave supports this function.
This item is fixed to "Checked" depending on the DP-Slave used.
• Not checked: Prohibits sending of Manufacturer Specific Alarm.
• Checked: Allows sending of Manufacturer Specific Alarm.
Check this box to allow Diagnostic Alarm to be sent.
This item can be set when the DP-Slave supports this function.
This item is fixed to "Checked" depending on the DP-Slave used.
• Not checked: Prohibits sending of Diagnostic Alarm.
• Checked: Allows sending of Diagnostic Alarm.