Slave status area (Alarm detection)
■Slave status area (Alarm detection) (Un\G26416 to Un\G26420)
This area stores alarm occurrence status of DP-Slaves. ( Page 32 Alarm acquisition function)
Address
Name
Un\G26416
All stations' alarm
status
Un\G26417 to Un\G26420
Each station's
alarm status
Address
b15
b14
Un\G26417
16
15
Un\G26418
32
31
Un\G26419
48
47
Un\G26420
64
63
The values in the table indicate which number of DP-Slave each bit represents.
Description
Stores the alarm detection status of all the DP-Slaves.
When an alarm has detected even on one DP-Slave in 'Each station's alarm status'
(Un\G26417 to Un\G26420), 1 is stored in 'All stations' alarm status' (Un\G26416).
• 0: No alarm detected
• 1: Alarm detected
When 1 is stored as 'All stations' alarm status' (Un\G26416), BF LED and DIA LED turn on.
The alarm detection status of each DP-Slave is stored by turning the appropriate bit on.
• 0: No alarm detected (including reserved stations, temporarily reserved stations, not-
configured stations, and alarm-unsupported stations)
• 1: Alarm detected in
b13
b12
b11
b10
b9
14
13
12
11
10
30
29
28
27
26
46
45
44
43
42
62
61
60
59
58
b8
b7
b6
b5
b4
9
8
7
6
5
25
24
23
22
21
41
40
39
38
37
57
56
55
54
53
Initial
value
0000H
0000H
b3
b2
b1
b0
4
3
2
1
20
19
18
17
36
35
34
33
52
51
50
49
APPX
Appendix 3 Buffer Memory
A
155

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents