Maintenance
Figure 78. Firmware Replacement
7 .
The upload will continue to run for about twenty minutes.
During this time, do not attempt to close any windows, remove the connect between the UPS and
upgrade PC, operate, work on, or remove any modules from the UPS.
8.
During the upload, the LCD screen on the UPS will blackout. This is normal and it will be fully operational
again once the upload is complete.
9.
When the upload is complete the progression window will disappear, however the log will be available for
review in the CSB/logs folder. A successful upgrade will look like the image below:
Figure 79. UPS CSB Firmware Installation Complete
10. Before attempting to run the application again fully power-cycle the UPS.