Initial Startup Parameters

NOTE
For a complete description of control panel operation menus and displays, see
Chapter 7 , "Control Panel Operation" on page 55.
The first time the UPS is turned on, you must set or verify certain operating parameters before placing the UPS
into operation. To set these initial configuration parameters:
1.
After the Eaton
buttons to scroll between English, French, and Spanish. Enter your selection by pressing the
E nglis h
Fra nça is
E s pa ñol
2.
Select the desired UPS output voltage using the
220,120/208, 120/240, 127/220 Vac. Press the
Output v olta ge
1 1 0 V
1 1 2 2 0 0 V V
1 1 2 2 7 7 V V
3.
Set the clock for the local time and date.
If the time or the date is correct as displayed, press the
l
setting. Time must be entered in 24-hour format.
If the time is incorrect as displayed, select the desired format and press the <- and -> buttons to move left
l
and right. Press the
displayed value is correct, press the
Date / Time
Format :
International
23
/ 05 / 2011 15 : 05
4.
Select 'Register product' from the menu and register your product with Eaton.
Menu
Setttings
Event log
Fault Log
Identification
Register product
5. The system signals an alarm when the required output cannot be maintained with the loss of redundant
power modules. The alarm is essentially disabled with a redundancy level set at 0.
6.
Optional. If you want the system to notify you when the number of redundant power modules is less
than a specified level, enter a redundancy level. Each increment above 0 indicates the number of modules
that can be removed from operation before the alarm occurs. This setting affects only the alarm; the
system continues to operate as an N+X system even if this parameter is left at the default value of 0 (see
also Figure 53 on page 62).
®
logo screen appears, select the desired language for the display. Use the
L a ngua ge
Y
B
and
buttons to increase or decrease the value of each selected digit. When the
Format :
MM/ DD / YYYY US
02 / 17 / 2017
Please register at:
www.eaton.com/pq
Type
Y
B
and
buttons. Possible selections are 100/200,110/
p
button when the desired output value is displayed.
p
button to advance to the next configuration
p
button.
Date / Time
03 : 05 pm
Eaton_9PXM
Eaton 9PXM UPS (4-20 kVA) User's Guide
UPS Startup
Y
B
and
p
button.
P-164000669—Rev 05