Page 40
9PX2200IRT3U 485 x 440 x 130 / 19.1 x 17.3 x 5.1 54.1 / 24.5 9PX3000IRT2U 605 x 440 x 86.5 / 23.8 x 17.3 x 3.4 60.8 / 27.6 9PX3000IRT3U 485 x 440 x 130 / 19.1 x 17.3 x 5.1 60.4 / 27.4 9PX3000IRTM 605 x 440 x 86.5 / 23.8 x 17.3 x 3.4...
Page 49
SAFETY INSTRUCTIONS Please keep this manual properly. This manual contains important instructions to follow for installation and maintenance of the UPS and batteries. The 9PX models that are covered in this manual are intended for installation in an environment within 0 to 40°...
Page 50
The system is not for use in a computer room AS DEFINED IN the standard for the Protection of Information Technology Equipment, ANSI/NFPA 75 (US installations only). Contact Eaton resellers to order a special battery kit, if needed to meet the ANSI/NFPA 75 requirement.
Page 51
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. If there are any questions, don’t hesitate to contact your EATON representative. •...
Page 52
HotSwap model) ..........................25 Communication............................27 Communication port ......................... 27 UPS remote control functions ......................28 Eaton Intelligent Power Software suite .................... 30 Operation ..............................31 Startup and Normal Operations......................31 Power on UPS with Battery ......................31 Power off UPS ..........................31 Operating modes ..........................
It is recommended that you read this manual thoroughly to fully understand the features of this UPS (Uninterruptible Power System) collection. Please read this manual before mounting. For a full list of Eaton product and related options, please visit our website at www.eaton.com/powerquality or contact your Eaton representative. 1.1 Environmental Protection Eaton has always been committed to protecting the environment by strictly abiding by relevant environmental protection policies.
Page 54
Material Abbreviation Code in symbol Polyethylene glycol terephthalate High-density polyethylene HDPE Polyethylene fluoride Low-density polyethylene LDPE Polypropylene Polystyrene Please follow all local regulations for disposal of waste packing materials. End of product life When the product reaches the end of its life, please make sure you follow all local waste disposal regulations for dismantling and destruction.
Appearance 2.1 Installations Tower installation Rack installation Model Weight Size (mm/in) (kg/lb) D x W x H 9PX1000IRT2U 21 / 46.3 450 x 440 x 86.5 / 17.7 x 17.3 x 3.4 9PX1500IRT2U 24.98 / 55 450 x 440 x 86.5 / 17.7 x 17.3 x 3.4 9PX1500IRTM 24.98 / 55 450 x 440 x 86.5 / 17.7 x 17.3 x 3.4...
Descriptions of indicator states: Indicator Status Description Green The UPS is in online mode or High Efficiency mode. Orange The UPS is in Battery mode. Orange The UPS is in Bypass mode. The UPS triggers an alarm or suffers from a fault. For more details, see Troubleshooting on Page 39.
2.7 User Settings The table below shows the options customizable by users. Sub-menu Available settings Default settings Local Settings Language [English] [French] [German] [Spanish] [Russian] [English] [Portuguese] [Italian] [Simplified Chinese] The user can select a [Japanese] preferred language Menus, statuses, notifications and alarms, UPS when the UPS is faults, event log data and settings are displayed energized for the first...
Page 62
Force Restart [Enabled] [Disabled] [Enabled] [Delay] [10s] ... [180s] [10s] If the main power supply is recovered during the shutdown sequence: If Force Restart is set to [Enabled], the shutdown sequence will be completed and the UPS will be restarted after 10 seconds. If Force Restart is set to [Disabled], the shutdown sequence will not be completed and the UPS will remain operational.
Page 63
Discharge [Yes] [No] [Yes] Protection If it is set to [Yes], the UPS will automatically adjust the battery voltage threshold at the end of battery discharge to prevent the battery from deep discharge. It set to [No], it will void the warranty. Communication Input Signal [ROO] [RPO] [DB9-4]...
Page 64
Shutdown [Delay Time Display] [Shutdown Control] Command [Shutdown Delay] [Restart] Sets Remote Power Off (RPO) related parameters. - [Delay Time Display]: [Yes] [No] Delay time display: [No] - [Shutdown Control]: [No] [UPS] [Partition 1] Shutdown control: [Partition 2] [Partitions 1+2] [No] - [Shutdown Delay]: [0s] …[999s] Shutdown delay: [0s]...
Installation 3.1 Inspecting the equipment If the equipment is damaged during shipment, please keep the carton and packing and lodge a freight damage claim with the carrier as soon as possible. If damage is discovered after acceptance, lodge a concealed damage claim as soon as possible. To lodge a freight damage claim or a concealed damage claim: Please lodge a claim with the carrier within 15 days of receiving the equipment;...
Page 66
Power cord fastener User's Manual disc Software download description Safety Manual Quick Start Instructions Guide rail Bracket (2 pcs) The following accessories are available depending on the model version or option. NMC (optional; standard configuration of the Netpack model) HotSwap MBP module (optional; standard configuration of the HotSwap model) Power cord connecting the HotSwap MBP module to the UPS •...
EBM Connection When you connect the EBM to the UPS, a small amount of arcs may be produced. This is normal and will not cause personal injury. Please quickly plug the EBM cable into the EBM port of the UPS. Plug the EBM cable into the battery connection port.
9PXEBM72RT3U 3.4 Connecting Other Accessories If you have ordered other UPS accessories, please refer to the corresponding User's Manual to check their connection with the UPS. 3.5 Tower installation If you have ordered other UPS accessories, please refer to the corresponding User's Manual to check their tower-type mounting to the UPS.
Page 69
• Adjust the orientation of the LCD panel and EATON logo. • Adjust the viewing angle of the LCD panel.
3.6 Rack installation • Rack-mount the UPS, EBM, and optional accessories modules. Follow Steps 1 to 4 to mount the module on the guide rail. The guide rail is supplied by Eaton.
UPS Connection - HotSwap MBP module not configured Please check the specifications on the nameplate on the back of the UPS, and pay attention to match the power distribution capacity. 9PX 1000I/1500I: Connect the UPS input socket ① to the AC power source with the power cord.
UPS Connection - HotSwap MBP module configured (optional; standard configuration of the HotSwap model) The HotSwap MBP module enables UPS servicing or even replacement without powering off the load. 9PX 2200IRT/9PX 3000IRT: Use the supplied power cord to connect the HotSwap MBP's input socket to the AC power supply.
Page 73
HotSwap MBP module usage The HotSwap MBP comes with a knob with two gears: Normal: The load power is supplied by the UPS and the indicator is on. Bypass: The load power is directly supplied by the AC power source and the indicator is on.
RS232 or USB communication port of the UPS. The UPS can now communicate with the Eaton power management software. NIC installation (optional; standard configuration of the HotSwap model) Shutting down the UPS is not required for NIC installation.
Features of contact point (optical coupling) • Voltage: Maximum 48VDC • Current: Maximum 25mA UPS remote control functions Programmable input signals 9PX has 3 input signal ports supporting signal programming: 1 RPO input port, 1 ROO input port, and 1 DB9 input port (Pin 4).
Page 76
RPO connection: Note Port type Terminal, up to Number 14 AWG wires Specifications of 60 VDC/30 VAC, maximum current: external switches 20 mA • Remote On/Off (ROO) ROO enables remote turning on/off the UPS via a switch. The UPS will be powered on (or remain on) when the contact point changes from an open circuit to a closed one.
Relay-MS card 4.3 Eaton Intelligent Power Software suite Eaton Intelligent Power Manager can be downloaded from eaton.com/downloads. The software provides up-to-date graphs of UPS power data and energy flow. It also provides a complete record of important power events and reminds you of important information about the UPS and power source.
Standby mode and the indicator will go off. 5.4 Operating modes For a description of the indicator statuses on the Eaton 9PX front panel, please refer to Page 11. Online Mode In Online mode, the indicator will light up and the UPS will be powered by the mains power grid.
You can minimize the heat dissipation from the UPS by setting High Efficiency mode and Low Energy Consumption mode. Please refer to “User Settings” on Page 14. Battery Mode If the mains power supply is interrupted while the UPS is running, the buzzer will beep every 1 second and indicator will light up.
5 minutes before switching to High Efficiency mode: If the bypass power supply quality exceeds the allowable range, the UPS will remain in Online mode. Eaton suggests you use HE mode only to protect IT devices. To set HE mode: Choose Settings >...
5.8 Configuration Battery Settings Auto Battery Detection Auto Battery Detection will be performed once a week in Constant Voltage Charge mode or per cycle in ABM Charge mode. The inspection period can be modified. During the test, the UPS will switch to Battery mode and discharge the battery for 10 seconds with load.
However, Eaton suggests you charge the battery for 48 hours after storing for a long period of time. Please check the battery charge date on the carton label. However, Eaton suggests you do not use the UPS if the date has elapsed and that the battery has never been charged. Please contact your local service representative.
• For the purpose of battery replacement, use batteries or a battery pack of the same model and quantity. Please contact your Eaton service representative to order new batteries. • Used and waste batteries shall be disposed of properly. Please refer to your local regulations for disposal requirements.
Page 84
To replace the battery pack: Remove the center cover from the front panel. Push the left cover to the right. Open the left cover. You will find a flat cable connecting to the UPS on the LCD control panel. Do not pull or disconnect the flat cable.
UPS Replacement - HotSwap MBP module configured The HotSwap MBP module enables UPS servicing or even replacement without powering off the load. Maintenance Set the switch to the "Bypass" position. The red LED indicator on the HotSwap MBP lights up, indicating that the load is directly powered by the AC input power supply.
Troubleshooting The Eaton 9PX supports long-term autonomous operation and issues warnings in the event of potential problems. In general, an alarm displayed on the control panel does not mean that the output power is affected, but is a preventive alarm to alert the user.
If there is a new alarm, the buzzer will beep again. 7.3 Service and Support For any questions about the UPS, please call your local distributor or your local service representative, or visit: powerquality.eaton.com Please have the following information ready before you seek help: •...
For critical applications, immediate replacement may be available. Please call the Help Desk for your nearest dealer or distributor. CE Certification Contact • Eaton I.F. SAS - 110 Rue Blaise Pascal - 38330 Montbonnot St Martin - France.
Specification 8.1 Model & Specification Bypass Input Output AC/DC DC/AC Filter Filter DC/DC Charger Battery Table 1. List of UPS Models Model Rated power 9PX1000IRT2U 1000VA / 1000W 9PX1500IRT2U 1500VA / 1500W 9PX1500IRTM 1500VA / 1500W 9PX2200IRT2U 2200VA / 2200W 9PX2200IRT3U 2200VA / 2200W 9PX3000IRT2U...
Page 90
Table 4. Electrical Input Nominal frequency 50/60Hz, automatic Frequency Range 40-70Hz before switching to Battery mode Bypass Voltage Range -20%/+15% nominal value (default) Default input Model Nominal input voltage Input voltage range (voltage/current) 9PX1000IRT2U 230V/10A 9PX1500IRT2U 230V/10A 9PX1500IRTM 9PX2200IRT2U 200V, 208V, 220V, 230V, Load = 100%: 176-276V 230V/12A 240V...
Page 91
The output is 102%~110% : overload alarm overload 110%~130% : turned off in 5 minutes (Bypass mode) 130%~150% : turned off in 15s >150% : turned off in 300ms Percentages are based on the nominal current values in Bypass mode. Voltage waveform Sine wave Harmonic distortion...
Page 92
Table 9. Battery Internal battery Rack-type/tower-type 1000VA: 48Vdc - 4 x 12V, 7Ah 9PXEBM48RT: mounting 1500VA: 48Vdc - 4 x 12V, 9Ah 48Vdc - 2 groups, 4 x 12V, 9Ah 2200VA: 72Vdc - 6 x 12V, 7Ah 9PXEBM72RT: 3000VA: 72Vdc - 6 x 12V, 9Ah 72Vdc - 2 groups, 6 x 12V, 9Ah Fuse 2.2K: 50A...
Glossary Bypass AC power supply Power source of the bypass. If maintenance is required in the event of UPS output overload or fault, the device can be switched to bypass power. Variable-frequency mode An operating mode to switch the AC power frequency (50Hz > 60Hz or 60Hz >...
Page 94
Marine Filter 3000 VA Installation and user manual...
Page 95
Introduction This product filters the low frequency noises produced by a UPS from 10 Hz to 150 KHz. Packaging UPS < = 2 k VA Installation Side Side Back Back Rack Mounting...
Page 96
Installation The socket-outlet shall be installed near the equipment and shall be easily accessible. 16A/16A or 10A/16A * 10A/16A 16A/16A UPS < = 2 k VA UPS > 2kVA Important safety instruction: Dangerous voltage levels are present within the filter. It should be opened exclusively by qualified service personnel. Technical specifications Marine Filter 3000 VA Power rating...