Operation
Battery Settings
The Battery Settings Menu provides control of battery tests, warnings and modes.
Local settings
In/Out settings
ON/OFF settings
Battery settings
Input signals
Comm settings
User Password Enable
User Password settings
Select Battery Settings
Figure 55. Battery Settings Menu
64
Eaton 9PXM UPS (4-20 kVA) User's Guide P-164000669—Rev 05
Settings
B attery settings
AB M On Off
Auto batter y test
Low battery warning
R estart batt. Level
Low BT R war ning
E x ternal battery
Deep disch. protect.
Select Battery Tests
and Warnings
ABM On Off
Disabled
Advanced Battery Mode
Enabled
[Enabled] [Disabled]
In ABM cycling mode:
[No test] [Every ABM cycle]
Auto battery test
In constant charge mode:
Disabled
[No test] [Every day]
Enabled
[Every week][Every month]
Default Value: [Every ABM cycle]/[Evey week]
[Capacity] [0%] ... [100%]
Low battery warning
[Runtime] [0min] ... [60min]
The alarm triggers when the
20
%
set percentage of battery capacity
or remaining back-up time is reached.
Default Value: [20%] [3min]
Restart batt . level
[0%]...[100%]
If set, automatic restart will
occur only when percentage
00
%
of battery charge is reached.
Default Value: [0%]
Low Battery Warning:
Low BTR warning
Below 3 min. or less than
setting capacity thershold.
180
sec
Default Value: [0%]
External battery
Auto detection
Go to bypass
Auto detection
Manual EBM set.
Manual battery set.
Battery settings
External battery
Auto battery test
Go to bypass
Auto
detectionss
Low battery warning
Auto detection
Restart batt. level
Manual EBM
Low BTR Warning
Manual battery
External battery
[Auto detection]
External battery
[Manual EBM set.]
Go to bypass
Manual EBM set.
[Manual battery set.]
Auto detection
Manual EBM set.
Manual battery set.
Default Value: [Auto detection]
Using standard EBM, UPS detects
automatically the number
of EBM connected
[Yes] [No]
.
.
If set to Yes, the UPS automatically
Deep disch
Protect
Warranty void if No
prevents battery from deep
discharge by adapting end of
No
back-up time voltage threshold.
Yes
Warranty void if set to No.
Default Value: [Yes]
External battery
Auto detection
Go to bypass
[Auto detection]
1EBM
External battery
Manual EBM set.
Go to bypass
set.
0
EBM
set.r
External battery
Go to bypass
Manual battery set.
0
Ah