Operation

In/Out Settings

The In/Out Settings menus allows control of input and output limits.
Local settings
In/Out settings
ON/OFF settings
Battery settings
Input signals
Comm settings
User Password Enable
User Password settings
Figure 53. In/Out Settings Menu
62
Eaton 9PXM UPS (4-20 kVA) User's Guide P-164000669—Rev 05
Settings
In/Out settings
Output voltage
High Efficiency mode
Protected Bypass
Overload prealarm
Redundancy
Byp freq limit
Byp volt min limit
Byp volt max limit
Output v olta ge
1 1 0 V
[110V] [120V][127V]
1 1 2 2 0 0 V V
1 1 2 2 7 7 V V
Default:[120V][127V]
High Efficiency mode
[Enabled] [Disabled]
Power the output from
Disabled
Enabled
Bypass for high efficiency
Default: Disabled
Protected Bypass
[Enabled] [Disabled]
Disabled
Default: Enabled
Enabled
Overload prealarm
[10%] ... [102%]
Load % when overload
100
%
alarm occurs
Default: 100%
Redundancy
Level 0
Level 1
Level 2
Level 2
Set redunancy level
Level 3
Default: 0
Level 4
Level 5
Default disables
Byp freq limit
transfer to Bypass if the
measured bypass
4
Hz
frequency is below
the nominal 4%
Default disables
Byp volt min limit
transfer to Bypass if the
measured bypass voltage
12
%
level is below the nominal
output voltage minus 12%
Default disables
Byp volt max limit
transfer to Bypass if the
measured bypass voltage
12
%
level is above the nominal
output voltage plus 12%