Operation

Comm Settings

The Comm Settings Menu enables/disables some selected control signal features.
Settings
Local settings
In/Out settings
ON/OFF settings
Battery settings
Input signals
Comm settings
User Password Enable
User Password settings
Select Comm Settings
Figure 57. Comm Settings Menu
66
Eaton 9PXM UPS (4-20 kVA) User's Guide P-164000669—Rev 05
Minislot 1 remote off
Disabled
Enabled
Minislot 2 remote off
Disabled
Enabled
Remote command
Disabled
Enabled
Comm Settings
Comm Settings
Minislot 1 remote off
Minislot 2 remote off
Minislot 1 remote off
Remote command
Minislot 2 remote off
Shutdown command
Remote command
Battery notice delay
Shutdown command
Minislot 1 reset
Battery notice delay
Minislot 2 reset
TBD
Battery notice delay
Comm Settings
Minislot 2 remote off
Minislot 1 reset
Remote command
Are you sure?
Shutdown command
Battery notice delay
Minislot 1 reset
Comm Settings
Remote command
Minislot 2 reset
Shutdown command
Are you sure?
Battery notice delay
Minislot 1 reset
Minislot 2 reset
Default Value: [Enabled]
TBD
Default Value: [Enabled]
[Enabled] [Disabled]
If Enabled, shutdown or restart
commands from software are
authorized.
Default Value: [Enabled]
Com Settings
Send command
Output off
Off delay
Restart
[0s] ... [99s]
Sets delay before displaying
on battery information
0s
to software..
Default Value: [0s]
[Yes] [No]
Yes
No
[Yes] [No]
Yes
No
[Send CMD] [Output off ]
[OFF delay][Restart]. Sets events
or fault that will actuate Output
signal parameters through
external contact connector or
RS232 port
[Send CMD]: Select [
] [Unselect]
[Output OFF]: Select [
] [Unselect]
[OFF delay]: [0s] ...[999s]
10s
[Restart]: [Yes] [No] authorized.
Default Values:
Send CMD: [Unselect]
Output OFF: Select [
]
Off delay: [10s]
Restart: Select [
]