Input Signal Wire Routing - Eaton 9PXM User Manual

Ups 4–20 kva
Hide thumbs Also See for 9PXM:
Table of Contents

Advertisement

Upper BPM Terminal Block
5
6
7
N
L1
AC FROM
UPS OUTPUT
Lower BPM Terminal Block
1
2
3
N
L1
AC TO LOADS
Figure 18. Bypass Switch Wiring Label and Terminal Blocks
10. After installing bypass switch wiring, torque the screws holding all input and output power conductors to
the values specified in Table 2 on page 16.

Input Signal Wire Routing

The auxiliary contacts must be wired to the BPM from the UPS for proper functionality. These
auxiliary contacts signal the UPS to go to Internal Bypass mode to provide a synchronized transfer.
Failure to wire the auxiliary contacts can be dangerous and result in system failure.
1.
Route the maintenance bypass signal wires in a conduit from the bypass module to the communication
signal terminal (CN13) on the rear of the UPS (see Figure 19).
2.
Place the signal wires through the proper conduit or grommet to the terminal block in the BPM
8
9
10
11
12
L2
N
L1
L2
AC LINE INPUT
4
13
14
15
16
L2
N
L1
L2
AC TO
UPS INPUT
CABLES FROM UPS AND AC
INPUT/OUTPUT THROUGH BPM
BOTTOM ACESS PLATE
CAUTION
Eaton 9PXM UPS (4-20 kVA) User's Guide
UPS with Bypass Electrical Installation
P-164000669—Rev 05
21