Eaton 9PX 6KVA Lithium-Ion
Advanced Users Guide
9PX6KIRTN-L
9PXEBM192RT2U-L
p/n: DPD-9PX2205
Revision 01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 9PX6KIRTN-L and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Eaton 9PX6KIRTN-L

  • Page 1 Eaton 9PX 6KVA Lithium-Ion Advanced Users Guide 9PX6KIRTN-L 9PXEBM192RT2U-L p/n: DPD-9PX2205 Revision 01...
  • Page 2 (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. ©Copyright 2022 Eaton, Raleigh, NC, USA. All rights reserved. No part of this document may be reproduced in any way without the express written approval of Eaton.
  • Page 3 S S a a f f e e t t y y o o f f P P e e r r s s o o n n s s • The system has its own power source (the battery). Consequently, the power outlets may be energized even if the system is disconnected from the AC power source.
  • Page 4 During the replacement of the Battery Module, it is imperative to use the same type and number of element as the original Battery Module provided with the UPS to maintain an identical level of performance and safety. If there are any questions, don’t hesitate to contact your local EATON representative.
  • Page 5: Table Of Contents

    6.1 Online Mode ............................27 6.2 Battery Mode ............................27 6.3 Bypass Mode ............................27 6.4 Standby Mode ............................27 6.5 Transferring Between Modes........................27 6.6 Setting High Efficiency Mode ........................28 6.7 Configuring Bypass settings........................28 Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 6 9 9 S S p p e e c c i i f f i i c c a a t t i i o o n n s s ......................................................... . 3 3 9 9 9.1 Model Specifications EMEA........................39 Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 7 To discover the entire range of Eaton products and the options available for the 9PX range, we invite you to visit our web site at www.Eaton.com...
  • Page 8: Environmental Protection

    With the Eaton 9PX, you can safely eliminate the effects of power disturbances and guard the integrity of your equipment. Providing outstanding performance and reliability, the Eaton 9PX’s unique benefits include: •...
  • Page 9 Description 9PXEBM192RT2U-L Extended Battery Module 4– post Rack Kit 9PX Network-M2 Gigabit Network Card Network-M3 Gigabit Network Card INDGW-M2 Industrial Gateway Card (Modbus TCP / RTU) INDRELAY-MS Industrial Relay Card Relay-MS Relay Card Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 10: Rear Panels

    Connector for RPO (Remote Power Off) control Connector for Hotswap / MBP detection Input / Output terminal blocks Slot for optional communication card Connector for additional battery module Connector for parallel operation Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 11: Control Panel

    Online mode Fault indicator (green) indicator (red) Battery mode Bypass mode indicator (orange) indicator (orange) Online mode 100% 2.7k W 30min 3.0kVA 1EBM Efficiency: 95 % Escape Down Enter On/Off button Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 12: Lcd Description

    The UPS is Off, waiting for startup Standby mode Equipment is not powered until command from user. button is pressed. The UPS is operating normally. The UPS is powering and protecting the Online mode equipment. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 13: Display Functions

    If the quantity of EBMs is reduced, UPS will report BMS comm. loss. If the quantity is increased, UPS cannot actively identify it. In those time, the user can select "BMS auto setup" to manually refresh the battery quantity. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 14: User Settings

    Frequency settable in frequency converter mode In/Out Output Mode [Industrial] [Industrial] [Network] settings Set UPS behavior regarding transfer on Bypass Input volt Sets input voltage hysteresis from [1] to |10V] [10V] hysteresis Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 15 The alarm triggers when the set percentage of battery capacity or remaining back-up time is reached. Battery settings Restart bat. [0%] ... [100%] [0%] level If set, automatic restart will occur only when percentage of battery charge is reached. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 16 User Settings Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 17: Unpacking The Cabinet

    The cabinet is heavy. Follow Special precautions provided and on the carton Unpack the equipment and remove all the packing materials and shipping carton. NOTE Do not lift the UPS or EBM from the front panel. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 18: Checking The Accessory Kit

    Input (2) cable lockers for 10A outlets Network card communication card (optional) (2) IEC 10A cables standard on network bundle models RS232 communication cable USB communication cable Safety instructions Quick Start Guide Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 19 Place the UPS on a flat, stable surface in its final location. Always keep 6" or 150 mm of free space behind the UPS rear panel for ventilation. If installing additional cabinets, place them next to the UPS in their final location. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 20: Tower Installation

    It is recommended that the UPS internal battery pack be removed before attempting to install the UPS in a Rackmount configuration. Follow Steps 1–6 on how to remove the battery pack from the UPS. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 21 I I n n s s t t a a l l l l i i n n g g t t h h e e U U P P S S o o n n t t h h e e R R a a i i l l s s Follow steps 1 to 5 for module mounting on the rails. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 22: Installation Requirements

    Screw back in the metal protection cover, connect the BMS connector together and install the screws for the front panel, then clip the center cover. The rails and necessary hardware are supplied by EATON. 3 3 . . 6 6 I I n n s s t t a a l l l l a a t t i i o o n n R R e e q q u u i i r r e e m m e e n n t t s s Recommended protective devices and cable cross-sections.
  • Page 23: Connecting The Ebm's

    EBM is connected, please note that the voltage difference between the different EBM’s should not be to large, less than 5V is recommended. Turn the DC breaker on each EBM to the “ON” position. See Figure 10 Figure Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 24 EBM Communication Wiring Battery Comm EBM 1 Battery Comm EBM 2 Battery Comm EBM 3 Battery Comm EBM 4 Figure 11. Tower EBM Connection EBM Communication Wiring EBM 1 EBM 4 EBM 2 EBM 3 Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 25: Installation Depending On The System Earthing Arrangement (Sea)

    Before carrying out any connection, check that the upstream protection device (Normal AC source) is open "O" (Off). Always connect the ground wire first If you ordered a HotSwap MBP, refer to the specific user manual to check the terminal blocks connection of the UPS with the MBP. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 26: Detecting Other Accessories

    3 3 . . 1 1 0 0 D D e e t t e e c c t t i i n n g g O O t t h h e e r r A A c c c c e e s s s s o o r r i i e e s s Tip If you ordered other UPS accessories, refer to specific user manuals to check the connection to the UPS. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 27: Communication Ports

    Pin 5: user common • Pin 6: on bypass • Pin 7: low battery • Pin 8: load protected • Pin 9: on battery • n.o.: contact normally open • n.c.: contact normally closed Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 28: Ups Remote Control Functions

    UPS when the Remote Power Off function is activated. Leave the RPO connector installed in the RPO port on the UPS even if the RPO function is not needed. RPO connections: Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 29 INDGW-M2 card- has SNMP and HTTP capabilities and a Modbus to facilitate remote monitoring of the UPS system through any Building Management System. • Relay-MS card- has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Battery low, UPS alarm/OK, or on Bypass. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 30 UPS or power information. If there is a power outage and the 9PX UPS battery power becomes low, Eaton Software suite can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
  • Page 31 UPS is operating normally and any loads are powered and protected. The UPS should be in Online mode. NOTE The internal batteries charge to 90% capacity in less than 3 hours. However, Eaton recommends that the batteries charge for 48 hours after installation or long-term storage.
  • Page 32: Ups Shutdown

    UPS starts to beep and shows a status of "UPS shutting OFF...". The UPS then transfers to Standby mode. Set the upstream circuit breaker (not provided) to the "O" position (Off) to switch off the utility power. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 33 From Online (or Battery) to Bypass mode. Press any button to activate the menu options, then select Control and Go to Bypass. From Bypass to Online (or Battery) mode. Press any button to activate the menu options, then select Control and Go back normal. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 34 10 ms when utility fails. Transfers to High Efficiency mode will be active after 5 minutes of Bypass voltage monitoring: if Bypass quality is not in tolerance, then the UPS will remain in Online mode. Eaton recommends to use the HE mode only to protect IT equipment. To set the High Efficiency mode: Select Settings, In/Out settings, and High Efficiency mode.
  • Page 35 The internal battery is heavy. Use caution when handling the heavy batteries. Eaton Lithium-ion UPS batteries have an expected life span of 8 years. After 8 years of operation, the UPS will provide a battery replacement notification reminding you that your batteries are nearing the end of their useful life.
  • Page 36: Replacing The Batteries

    Figure 15. Internal Battery Pack Replacement To replace the battery pack: Remove the center cover of the front panel. Remove the two screws to open the left side of the front panel. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 37: Battery Settings Reset

    “Control” option. Press Press the to display the “BMS auto setup” or “Reset battery life” option of the control menu. Press the button and use the to select “Yes”. Press the button to reset. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 38: Online Mode

    If the UPS internal batteries and external battery packs were replaced and the UPS was powered off: Verify that the internal batteries are connected. See Figure 15 If optional EBMs are installed, verify that the EBM are connected to the UPS. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 39 This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 40 Recycling The Used Equipment Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 41 T T y y p p i i c c a a l l A A l l a a r r m m s s a a n n d d F F a a u u l l t t s s The Eaton 9PX are designed for durable, automatic operation and also alert you whenever potential operating problems may occur.
  • Page 42: Silencing The Alarm

    Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition and perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 43: Service And Support

    C C o o m m p p l l i i a a n n c c e e C C o o n n t t a a c c t t • Eaton I.F. SAS - 110 Rue Blaise Pascal - 38330 Montbonnot St Martin – France. •...
  • Page 44: Compliance Contact

    Compliance Contact Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 45 50Hz : 40-60Hz before transfer to battery 60Hz : 50-70Hz before transfer to battery Bypass Voltage Range -20% / +15% of nominal value (default) Noise Filtering MOV for normal and common mode noise Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 46: Battery Mode

    Output Short Circuit max RMS & delay time: 56.5A/150ms; The max peak value: 92A Table 13. Electrical Output Connections Model Output Connection Output Cable 9PX6KIRTN-L (2) IEC 10A Hardwired (2) IEC C19 (8) IEC C13 Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 47 < 45 dBA at 1 meter typical UPS enclosure IP rating: IP20 Protective class: Class I Power system: TN/TT/IT Table 15. Battery Internal Batteries Rack / Tower configuration 9PX6KIRTN-L: 192Vdc 9PXEBM192RT2U-L: 192Vdc Type Lithium Iron Phosphate (LFP) battery module Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 48 RS-232 (DB9): 1200-19200 bps USB: 19200 bps Relay Output Contacts (4) relay outputs (normally open or normally closed) Remote On/Off 2 pins jumper (normally open) Remote Power Off 3 pins jumper (normally open or normally closed) Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 49 Model Specifications EMEA Eaton 9PX Lithium-Ion User Guide DPD-9PX2205—Rev 01...
  • Page 50 DPD-9PX220501 DPD-9PX2205 01...