Walktest Ending Sequence; Voice Activations - Siemens FIREFINDER-XLS Operation Manual

Table of Contents

Advertisement

PMI OPERATION MANUAL

Walktest Ending Sequence

Voice Activations

3-20
MAINTENANCE MODE
Technical Manuals Online! - http://www.tech-man.com
When No Bells is selected, there is no audible notification of Walktest events.
There is no event-type coding during the Walktest. Audible notification is the same
for Alarm, Supervisory, Security and Trouble events.
If the system has a report printer, Walktest events will be printed with the Walktest
designation "WT" and the event type. The Walktest event types are as follows:
W
A
L
K
T
E
S
T
E
V
E
N
T
T
Y
P
E
P
i r
t n
r e
E
v
e
t n
T
y
p
e
D
e
s
g i
n
t a
o i
l A
r a
m
W
T
A
L
M
S
u
p
e
v r
s i
o
y r
W
T
S
U
P
S
c e
r u
y t i
W
T
S
E
C
T
o r
u
b
e l
W
T
T
R
B
t S
t a
s u
W
T
S
T
A
Trouble conditions will continue to be reported for devices in Walktest.
Five minutes before the end of the Walktest, a 15-second audible activation occurs.
When the Walktest is set for Group Bells, only audibles located in the group being
tested will sound; when set for All Bells, all of the audibles will sound. When the
Walktest is set for No Bells, only the strobes will activate. The audibles will sound
in a two seconds on - one second off pattern. The strobes will be on steady and will
be either synchronized or unsynchronized, depending on the system setting.
Do not perform any further Walktest activations after the 5-minute warning or 5
minutes prior to the expiration of the Walktest or the planned cancellation time.
Forty-five seconds before the end of the Walktest, a 45-second audible activation
occurs. When the Walktest is set for Group Bells, only audibles located in the group
being tested will sound; when set for All Bells, all of the audibles will sound. When
the Walktest is set for No Bells, only the strobes will activate. The audibles will
sound in a two seconds on - one second off pattern. The strobes will be on steady
and will be either synchronized or unsynchronized, depending on the system
setting.
Zone coding will not be performed during a Walktest.
The volume for the Walktest channel is set low. During Walktest, speaker zones are
activated steady. The duration for each activation type is the same as for ZIC activation.
The tone specified for Walktest is File 1 Tone 1. The user may program a tone or
message to that tone location using the Zeus programming tool. Use caution when
selecting the tone or message. An inappropriate tone or message during a Walktest
might be disruptive.