Summary of Contents for Siemens Cerberus PYROTRONICS MXL
Page 1
Cerberus Division Table of Contents Version 1.0 This CD-Rom contains the information necessary to install, operate and maintain the Siemens, Cerberus Division MXL/MXLV and MXL-IQ Fire Protection Control Panels Contents Personalize/ MXL/MXLV Control Panel Printout Cover P/N 315-092036CD-8 MXL-IQ Control Panel...
Page 2
Cerberus Division CERBERUS PYROTRONICS MXL/MXLV CONTROL PANEL Operation, Installation, and Maintenance Manual Siemens Building Technologies, Ltd. Siemens Building Technologies, Inc. 50 East Pearce Street 8 Fernwood Road Richmond Hill, Ontario L4B 1B7 CN Florham Park, New Jersey 07932 P/N 315-092036CD-8 Technical Manuals Online! - http://www.tech-man.com...
Page 3
WARNING UL Listings for MXL/MXLV must not be used For additional wiring information, refer to this manual or call Siemens Building Appendix D - MXL Power Supply Technologies, Inc. Load Calculations Technical Support Department at 1-800-248-7976. Technical Manuals Online! - http://www.tech-man.com...
Page 4
Table of Contents Chapter 1 Description ..............1 - 1 Introduction ........................1 - 1 Software ........................... 1 - 3 Components of the Basic MXL System ............... 1 - 3 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 5
Table of Contents The Voice System (MXLV) .................... 1 - 20 Analog Addressable Devices ..................1 - 33 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 13
Table of Contents Appendix Glossary Index Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 14
Description CERBERUS PYROTRONICS CERBERUS PYROTRONICS Any Alarm Trouble. Using the Menu in Chapter 3 - Operation Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 22
If you install a printer in that backbox, only two MOM-4s can be installed. Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 58
Installation Connections and Ratings Installing the NET-7M onto the PSR-1 Do not touch the Installing the Card Guides on the MOM gold plated card edge. Connections and Ratings Installing the MOM or OMM Installing Card Guides on the MOM Mounting the MOM Card Cage 2 - 7 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 61
Installation Hold the paper with both hands and gently pull until eight inches of paper extends out from the printer. Feed the paper through the slot in the guide plate. Return the guide plate to its normal position and secure it with the two knobs.
Page 66
Installation BTC-1 TONE SWITCH SETTINGS Setting Tone EVAC ALERT 8 7 6 5 4 3 2 1 O O O O O O O O DO NOT USE O O O X O O O X Chime O O X O O O X O 2000 Hz O O X X...
Page 68
Installation MHD PANELS MHD PANELS Model Purpose Location Mounting CONTROL PANEL*: Place in second group of four holes by hinge Use middle position (Printer available) Dead front barrier with cutout for MHD-1 printer when needed REMOTE PANEL: Place in first and/or second group of four holes Use top or middle position (No printer) MHD-2 Dead front barrier only...
Page 70
Installation VSM-1/VLM-1/VFM-1 SWITCH SETTINGS Address 6 5 4 3 2 1 Address 6 5 4 3 2 1 Illegal O O O O O O O X O O O O O O O O O X O X O O O X O O O O X O O X O O X O O O O O X X...
Page 71
Remember, the cables are polar- ized, do not force them. The cables are polarized; do not force them. Connections and Ratings Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 72
Installation before Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 74
Installation SETTING THE MODE OF OPERATION - CSM-4 (USING S3, S4 AND G1, G2) For Circuit 1 Position Notification Appliance Circuits Not Cut Municipal Tie (NFPA 72B) Remote Station (NFPA 72C) Not Cut Releasing Service (NFPA 12A)* Releasing Service (NFPA 13)* Releasing Service (NFPA 2001)* Illegal (Results in a trouble on CSM-4) For Circuit 2...
Page 75
SETTING THE DEGRADE TROUBLE MODES ON S2 - CSM-4 For Circuit 1 Leased Line Trouble On (Closed) No Trouble Activation Off (Open) For Circuit 2 Leased Line Trouble On (Closed) No Trouble Activation Off (Open) NOTE: If circuit 1 or circuit 2 is not used for leased line trouble, switches SW1 or SW2 must be off (open).
Page 78
Installation FSI PROGRAMMING Address 8 7 6 5 4 3 2 1 O O O O O O O O O=Open or OFF AnaLASER PROGRAMMING Address 8 7 6 5 4 3 2 1 AnaLASER X O O O O O O O O=Open or OFF X=Closed or ON Technical Manuals Online! - http://www.tech-man.com...
Page 79
NIM-1R PANEL NUMBER PROGRAMMING (S2) Address 8 7 6 5 4 3 2 1 Address 8 7 6 5 4 3 2 1 Address 8 7 6 5 4 3 2 1 Address 8 7 6 5 4 3 2 1 R O O O O O O O S O O X O O O O S O X O O O O O...
Page 84
Installation ASC-1 S2 SETTINGS Address 4 3 2 1 Address 4 3 2 1 ILLEGAL O O O O X O O O O O O X X O O X O O X O X O X O O O X X X O X X O X O O ILLEGAL...
ASC-2 S1 SETTINGS ASC-2 S2 SETTINGS Address 4 3 2 1 Address 4 3 2 1 Amplifier Input ILLEGAL O O O O X O O O Riser 1 Riser 2 Riser 3 ILLEGAL O O O X X O O X O O X O X O X O O O X X...
Page 87
BTC-1 TONE SWITCH SETTINGS Setting Tone EVAC ALERT 8 7 6 5 4 3 2 1 O O O O O O O O DO NOT USE O O O X O O O X Chime O O X O O O X O 2000 Hz O O X X...
Page 90
Installation ZC1-8B S1 SETTINGS ZC1-8B S1 SETTINGS Address 5 4 3 2 1 Address 5 4 3 2 1 ILLEGAL O O O O O O X O O O O O O O X O X O O X O O O X O O X O X O O O O X X...
Page 91
ZC2-8B S1 SETTINGS ZC2-8B S1 SETTINGS Address 4 3 2 1 Address 4 3 2 1 ILLEGAL O O O O X O O O O O O X X O O X O O X O X O X O O O X X X O X X O X O O...
Page 92
Installation ZC3-4AB S1 Settings ZC3-4AB S1 SETTINGS ZC3-4AB S1 SETTINGS Address 4 3 2 1 Address 4 3 2 1 ILLEGAL O O O O X O O O O O O X X O O X O O X O X O X O O O X X X O X X...
Page 94
Installation ZCT-8B S1 SETTINGS Address 4 3 2 1 Address 4 3 2 1 ILLEGAL O O O O X O O O O O O X X O O X O O X O X O X O O O X X X O X X O X O O ILLEGAL...
Page 96
Installation ZAC-30 S1 SETTINGS Address 4 3 2 1 Address 4 3 2 1 ILLEGAL O O O O X O O O O O O X X O O X O O X O X O X O O O X X X O X X O X O O ILLEGAL...
Page 99
NETWORK ADDRESS PROGRAMMING TABLE NETWORK ADDRESS PROGRAMMING TABLE ADDR ADDR ADDR ADDR & % $ # " ! & % $ # " ! & % $ # " ! & % $ # " ! I L L E G A L O X O O O O O O X O O O O O O O X X O O O O O O...
Operation * In this chapter, MKB refers to all of the following MKB models: MKB-1, MKB-2, MKB-3, and MKB-4. Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 156
Enter to proceed, other key to abort History Manually Erased History Manually Turned off History Manually Turned on Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 157
HISTORY EVENTS BY GROUP Event Type Event Modifier Alarm block acknowledge No modifiers for this group. Trouble block acknowledge Security block acknowledge Supervisory block acknowledge Manual reset via MKB Hard reset from power off Hard reset via reset jumper Hard reset via watchdog Alarm verify Energize an output De-energize an output...
Page 168
Chapter Connections and Ratings ACM-1 Connections and Ratings Electrical ratings: Connect the 14-conductor ribbon 24VDC, 85mA cable (P/N 555-192236) from the TMM-1, P3 to P1 on the ACM-1, if 5VDC, 176mA used. Connect the 50-conductor ribbon Electrical connections: cable (P/N 555-192201) from the The ACM-1 can be wired in two TBM-1/-2, P3 to P2 on the ACM-1.
Page 169
ACM-1 Connections and Ratings Wiring an ACM-1 that is Mounted on an MKB-2 Wiring an ACM-1 in a Remote Expander Enclosure 4 - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 170
ALD-2I Connections and Ratings Electrical ratings: Only the devices listed in Appendix A, Supervisory 30 VDC peak Table 2 - Analog Addressable Detec- 66mA max tors on page A-1 may be used. The UL identifiers for compatibility are the same Alarm 30 VDC peak as the model names specified.
Page 178
CMI-30 CMI-30 onnect onnect ions and R ions and R at at at at at ings ions and R ings ings CMI-30 0 C 0 C onnect onnect ions and R ings CMI-30 CMI-30 onnect ions and R ings Electrical ratings: Supervisory or Alarm 5 VDC, 96mA max TYPICAL CLASS B (STYLE 4)
Page 179
CMI-300 Connections and Ratings NOTES 1. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 2. All circuits are rated 2 volts peak to peak, 1.3mA. All circuits are supervised. 3. Operates in full conformance with Style 7.
Page 180
CRM-4 Connections and Ratings Electrical ratings: 24 VDC 15mA (no energized relays) Add: 18.7mA per energized relay (75mA - all relays energized) NOTES 1. Contact rating: 2A, 30VDC/120 VAC resistive. 2. Use only with power limited / Class 2 MOM-4 circuits.
Page 182
CSM-4 C CSM-4 C onnect onnect ions and R ions and R at at at at at ings ions and R ings ings CSM-4 C onnect onnect ions and R ings CSM-4 C CSM-4 C onnect ions and R ings Only the devices listed in Compatible Notification Appliances, P/N 315- 096363 may be used.
Page 183
CSM-4 Connections and Ratings MUNICIPAL TIE Electrical ratings: (NFPA 72 Municipal Tie) Trip Coil 14.5 ohms All wiring must be in accordance with Trip Current 220 to 320mA Article 760 of NEC and the local DC (momentary) building codes. Supervisory Current 12mA DC Voltage...
Page 184
CSM-4 Connections and Ratings MOM-4 (TB1, TB2, TB3,or TB4) MOM-2 (TB2 or TB4) CSM-4 Leased Line Circuit Wiring RELEASING SERVICE (Per NFPA 12A, Electrical Ratings: NFPA 13, and NFPA 2001) Solenoids 24 VDC All wiring must be in accordance with 16.8 watts max Article 760 of NEC and the local build- 700mA max...
Page 185
MXL Releasing Service Wiring (per NFPA 12A, NFPA 13, and NFPA 2001) firealarmresources.com...
CZM-1B6 Connections and Ratings Electrical ratings: Initiating Devices Appendix A, Table 1 - Conventional Detectors: Compatible With CZM-1B6 Electrical connections: STYLE B (CLASS B) STYLE D (CLASS A) POWER POWER EARTH EARTH ANALOG LOOP ANALOG LOOP CZM-1B6 Class B (Style B) Wiring CZM-1B6 Class A (Style D) Wiring 4 - 19 Technical Manuals Online! - http://www.tech-man.com...
Page 188
CZM-1B6 Connections and Ratings CZM-1B6 Power PSR-1 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 CZM-1B6 Power Wiring 4 - 21 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 189
CZM-1B6 Connections and Ratings WARNING: Intrinsically Safe Zone Wiring FM Approved Only (Not UL Approved) 4 - 22 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 190
CZM-4 Connections and Ratings Electrical ratings: Initiating devices per zone: Supervisory 21.7-22.8 VDC Up to 30 detectors, any combination of 4mA max those listed in Appendix A, Table 1 - Conventional Detectors (except the Alarm 21.7-22.8 VDC PBA-1191), on page A-1, may be used. 180mA per zone max Up to five waterflow switches or 20 tamper switches may be used.
Page 192
D2300CP Connections and Ratings Electrical ratings: RS-485 Network not connect the terminal marked GRD. Indicators Fiber Connections 4 - 25 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 193
D2300CP Connections and Ratings 5 VDC Current Calculation Supply Load Calculations PS-5A Installation Instruc- tions Appendix D - MXL Power Wiring the D2300CP as Both a Repeater and End Point Unit 4 - 26 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 194
D2300CP Connections and Ratings Wiring the RS-485 Network in Style 4 Wiring the RS-485 Network in Style 7 4 - 27 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 196
DMC-1 Connections and Ratings Electrical ratings: J1 audio input level 10mV RMS nominal 5 VDC, 50mA (25mV RMS max.) Auxiliary power supply input for J2 audio input level 500 mV RMS nominal manual recording on bench only (1.5V RMS max.) (Use any UL listed 12 VDC regulated power supply): Total time for all custom...
Page 198
ICP-B6 Connections and Ratings Analog Loop ALD-2I ALD-2I MOM-4 MOM-4 LOOP 1 LOOP 2 LOOP 1 LOOP 2 LOOP 1 LOOP 2 LOOP RESISTANCE 100 OHMS MAX 18 AWG MINIMUM WIRE NO EOL DEVICE REQUIRED SUPERVISED, POWER LIMITED PER NEC 760 Analog Loop Wiring ALL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL CODES...
ICP-B6 Connections and Ratings The ICP-B6 module can be used in four When used as an NAC module, the different ways: output circuit is power limited. The ICP-B6 maximum current is 1.5A at 24 VDC. If the 24 VDC is lost or the NAC 1.
Page 200
ICP-B6 Connections and Ratings ICP-B6 Wiring Using TRI-60/B6 ICP-B6 Wiring Using PSR-1 4 - 33 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 201
ICP-B6 Connections and Ratings 2. Using the ICP-B6 as a Telephone Zone 3. Using the ICP-B6 as a 70 Volt Speaker Zone ASC-2 Instruc- isolate them from the system tions, circuits and the earth ground the shield is continuous and isolated from both system circuits and earth ground and that the shields are connected together using terminal 5 of TB2.
Page 202
NOTES 1. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 2. The shield on the common talk riser must be continuous and connected only to DC common at the TBM. 3. Each FJ303 has a factory installed 10K EOL resistor.
Page 204
ICP-B6 Connections and Ratings 4. Using the ICP-B6 as a 25 Volt Speaker Zone ASC-2 Instructions, Approximate Speaker Zone Wire Loss with the 70.7V Option Approximate Speaker Zone Wire Loss with the 25V Option 4 - 37 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 205
ICP-B6 Used as a 25V Speaker Zone firealarmresources.com...
Page 206
MMB-2 Connections and Ratings 24V power connection. MPS-6/6W- Be sure that the jumper assembly is installed in P14 of the MMB-2. If this jumper is not in- stalled, the MMB-2 will detect a permanent AC fail or indicate auxil- iary power voltage is low. MPS-12/12W - 5V power and the communication interface.
MMB-2 Connections and Ratings CZM-1B6 power Auxiliary power is available on TB5, terminals 9 through 12. The circuit is power limited per NEC Article 760 and is rated at 1 amp, 18-31 VDC. This power supply is for use with the CZM-1B6 Remote Conventional Zone module.
Page 208
Appendix A, Table 2 - Analog Addressable Detec- tors Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
MMB-2 Connections and Ratings Notification appliance circuits Common Alarm Relay (TB5, 1-4 and TB5, 5-8) The common alarm relay changes state These circuits are for notification whenever a fire alarm is detected. appliances only, NFPA 72 Local. For NFPA 72 Municipal Tie or NFPA 72 Common Supervisory Relay Leased Line, use the Model CSM-4.
Page 210
NOTE: e t t Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 212
MOI-7, MOD-16, MID-16 Connections and Ratings MOI-7 The second connection Electrical ratings: except must Electrical connections 5V Power Do not use connector P5 in this configuration. The third connection MXL Network Connection The first connection Do not use connector P5 in this configuration. 4 - 45 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 213
MOI-7, MOD-16, MID-16 Connections and Ratings MOD-16 and MID-16 Connection Remove ICs U1 and U12 and make no connections to TB1. 24V Return MOD-16 and MID-16 Wiring (Figure 1) 4 - 46 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 214
MOI-7, MOD-16, MID-16 Connections and Ratings Local Trouble Input Local Lamp Test MXL Network Wiring (Figure 2) 4 - 47 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 215
MOI-7, MOD-16, MID-16 Connections and Ratings MOI-7 Wiring in Same Enclosure (Figure 3) MOI-7 Power The PSR-1 may be used in stand-alone connected as a means of reporting mode as the power supply for the PSR-1 troubles to the MXL. MOI-7.
Page 218
MOM-2 Connections and Ratings Electrical Installation MMB-2 Installation Instructions PSR-1 Installation Instructions MAXIMUM MODULE LOAD CURRENTS Source Max. Current MMB-2 with MPS-6/6W MMB-2 with MPS-12/12W 12 * PSR-1 with MPS-6/6W 6 ** PSR-1 with MPS-12/12W 12 ** * Derate by the total of CZM-1B6 power, NAC-1 and NAC-2 ** Derate by the total of CZM-1B6 power 4 - 51 Technical Manuals Online! - http://www.tech-man.com...
Page 219
MOM-2 Connections and Ratings EXAMPLE: Appendix D - MXL Power Supply Load Calculations With MPS-6/6W: NOTE: With MPS-12/12W: 4 - 52 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 220
MOM-4 Connections and Ratings Electrical Installation MMB-2 Installation Instructions PSR-1 Installation Instructions MAXIMUM MODULE LOAD CURRENTS Source Max. Current MMB-2 with MPS-6/6W MMB-2 with MPS-12/12W 12 * PSR-1 with MPS-6/6W 6 ** PSR-1 with MPS-12/12W 12 ** * Derate by the total of CZM-1B6 power, NAC-1 and NAC-2 ** Derate by the total of CZM-1B6 power 4 - 53 Technical Manuals Online! - http://www.tech-man.com...
Page 221
MOM-4 Connections and Ratings EXAMPLE: Appendix D - MXL Power Supply Load Calculations With MPS-6/6W: NOTE: With MPS-12/12W: 4 - 54 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
NIM-1R C NIM-1R C onnect onnect ions and R ions and R at at at at at ings ions and R ings ings NIM-1R C onnect onnect ions and R ings NIM-1R C NIM-1R C onnect ions and R ings Electrical ratings: Installation Instructions, P/N 315- 5 VDC, 160mA...
Page 226
OCC-1 Connections and Ratings Electrical ratings: Maximum loop resistance: 24 VDC, 17mA 20 ohms for all wires 5 VDC, 22mA End of Line Resistors All wiring must be in accordance with Audio risers: 10K, ½W, 5% Article 760 of NEC or the local building P/N 140-820396 codes.
Page 227
OCC-1 Connections and Ratings PLC-4/PL864 Installation Instructions PLACE AMPLIFIER INPUT AND OUTPUT CABLES IN SEPARATE CONDUITS Wiring the OCC-1 4 - 60 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 232
PIM-1 Connections and Ratings Electrical ratings: RS-232C Interface : ±12 VDC : ±5mA Maximum cable length 25 feet (2 ohms max per circuit) NOTES 1. Terminals TB1-8 and 9 are connected together Leave jumper G1 in on the PIM-1. place if the System 2.
Page 234
PIM-2 / PAL-1 Connections and Ratings PIM-2 SERIAL INTERFACE COMMUNICATION PARAMETERS Dipswitch Position (SW1) - Located at rear of PIM-2 Baud Rate 9600 4800 2400 1200 Data Bits Parity Even Parity Disable Enable Flow Control Hardware Software Port Type NOTE: When setting switch S1, OFF = UP = OPEN ON = DOWN = CLOSED UPS Wiring for PIM-2...
Page 240
PS-5A Connections and Ratings Electrical ratings: Input 18-31 VDC 300mA max J1: 24V feed through 250mA max Output J2 and J3: 5 VDC, 1A max (Total current on J2 and J3) NOTES Wiring restricted to the same room and within conduit, not to exceed 20 ft.
PS-5N7 Connections and Ratings Electrical ratings: Using the PS-5N7 with Style 4 (2-Wire) Network Connections Using PS-5N7 with Style 7 (4-Wire) Network Connections PS-5N7 Power Supply and Network Wiring 4 - 75 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 243
PS-5N7 Connections and Ratings Using the PS-5N7 to Drive an OMM-1 POWER RESTRICTIONS (5V max current = 500mA) OMM-1 OCC-1 22mA ASC-1 29mA ASC-2 29mA ZC1-8B 31mA ZC2-8B 31mA ZC2-4AB 30mA ZC3-4AB 28mA ZCT-8B 33mA PS-5N7 and OMM-1 Wiring 4 - 76 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 244
PS-5N7 Connections and Ratings PS-5N7 in a Remote Extender Enclosure Wiring 4 - 77 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 246
PSR-1, NET-4, NET-7, NET-7M Connections and Ratings Primary power Battery backup Appendix C - MXL Battery Calculations MPS-6/6W Making the network connection (TB4) MPS-6/6W Installation Instruc- tions Be sure that the jumper assembly is installed in P10 of the PSR-1. If this jumper is not installed, the PSR-1 will detect a permanent NET-7 Installation AC fail or indicate auxiliary power...
Page 247
PSR-1, NET-4, NET-7, NET-7M Connections and Ratings NET-4 Electrical Ratings: NET-4 Wiring NET-7 End of line resistors: Electrical ratings: 4 - 80 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 250
PSR-1, NET-4, NET-7, NET-7M Connections and Ratings Wiring Auxiliary power for CZM-1B6 and PS-5A (TB3) Two relays are provided on the PSR-1 A Class A power limited output is provided for local control of alarm and trouble on TB3, terminals 3-6 for use with the indication.
Page 251
PSR-1, NET-4, NET-7, NET-7M Connections and Ratings Class B wiring can be used to obtain the maximum of 40 CZM-1B6s. Each Class B wire run can support a maxi- mum of 20 CZM-1B6s, 4 ohms max. CLASS B WIRING 18-31 VDC Multiple Class B power connections 2A MAX POWER LIMITED TO...
Page 254
RCC-1/-1F Connections and Ratings Electrical ratings: All wiring must be in accordance with RCC-1/-1F 14 to 31 VDC, Article 760 of NEC and the local 80mA max building codes. Battery current 75mA RCC-1/-1F 14 to 31 VDC, with PIM-1 100mA max Battery current 95mA NOTES...
Page 256
RCM-1 Connections and Ratings Electrical ratings: LLM-1 Installation Instructions PORT STYLE FUNCTION Audio signal input Modes of Operation Audio signal input/output Audio signal output Audio signal output Local Mode - Global Mode 1 - Global Mode 2 - RCM-1 Ports 4 - 89 Technical Manuals Online! - http://www.tech-man.com...
Page 257
RCM-1 Connections and Ratings RCM-1 APPLICATIONS Application Number (See Corresponding Configuration Diagram) Typical Style 4 Installation Style 4 Installation with a Style 4 Output Only Extension Typical Style 7 Installation Style 7 Installation with a Style 4 Extension Style 4 Installation with Fiber Optic Transmission Style 4 Fiber Optic with a Style 4 Fiber Optic Output Only Extension Style 7 Fiber Connection with a Style 4 Output Only fiber...
Page 258
RCM-1 Connections and Ratings Application 3: Typical Style 7 Installation Application 4: Style 7 with a PORT C Extension Application 5: Style 4 Fiber Optic Installation 4 - 91 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 259
RCM-1 Connections and Ratings Application 6: Style 4 Fiber Optic with a PORT C Fiber Optic Extension Application 7: Style 7 Fiber Optic with a PORT C Fiber Optic Extension 4 - 92 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 261
RCM-1 Connections and Ratings S2 SETTINGS Typical Style 4 connections Location Location Location Description Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2. Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms.
Page 262
RCM-1 Connections and Ratings S2 SETTINGS Typical Style 4 connections with Location Location Location Location Location Description PORT C extension Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2.
Page 263
RCM-1 Connections and Ratings Typical Style 7 connections S2 SETTINGS Location Location Location Location Description Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2. Limit the maximum resistance of loop total from the first RCM to the last RCM...
Page 264
RCM-1 Connections and Ratings S2 SETTINGS Style 7 connections with PORT C Location Location Location Location Description extension Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2. Limit the maximum resistance of loop total from the first RCM to the last RCM...
Page 265
RCM-1 Connections and Ratings S2 SETTINGS Typical Style 4 fiber optic connections Description As Shown with optional PORT C extension - Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire.
Page 266
RCM-1 Connections and Ratings S2 SETTINGS Typical Style 7 fiber optic connections Description As Shown with optional PORT C extension - Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire.
Page 267
RCM-1 Connections and Ratings S2 SETTINGS Combination fiber and wire Style 4 Location Location Location Description connection Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2. Limit the maximum resistance of loop total from the first RCM to the last RCM...
Page 268
RCM-1 Connections and Ratings S2 SETTINGS Style 4 Repeater Connection Location Location Description Copper config Copper config Copper config Copper repeater Fiber config Fiber config Style 7 NOTES 1. Use 18 AWG minimum wire. 2. Limit the maximum resistance of loop total from the first RCM to the last RCM to 100 ohms.
Page 269
RCM-1 Connections and Ratings RCM Style 4 connections to the OCC RCM Style 6 connections to the OCC RCM Style 4 connections to the ACM RCM Style 6 connections to the ACM Wiring Configurations for the OCC and ACM 4 - 102 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 270
REP-1 Connections and Ratings Electrical ratings: Input voltage 24 VDC Input current 40mA at 24 VDC Battery Current 40mA at 24 VDC T-Tap Running In One Direction with Style 4 Basic Repeater - Style 4 T-Tap Running in Two Directions with Style 4 (TO RCC-1 /-1F OR MOI-7...
Page 271
REP-1 Connections and Ratings Electrical connections: The new repeated network begins at A basic repeater connects to the net- the REP-1 and also has an end of line work at the end of the run. A repeater resistor. In a Style 4 network the can extend the distance of the network second half of the REP-1 is not used, or can add more nodes to the system.
Page 272
Silent Knight Model 5128/5129 Connections and Ratings Electrical ratings: Electrical connections: Silent Knight 5128/5129 Fire Slave Communicator Installation Manual 4 - 105 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 273
CZM-1B6 POWER CHASSIS NOT SUPERVISED MMB-2 (RED) P1 - DC POWER TELCO 1 RING (GREEN) (BLK) (YLW) SUPERVISED SUPERVISORY TELCO 1 TIP (RED) (ORN) SILENT KNIGHT 5230 (RED) (PROGRAMMING) TROUBLE (BRN) HOUSE 1 TIP (GRAY) (GRY) TO RJ31X ALARM (VIO) HOUSE 1 RING (BROWN) (BLU) (GRN)
Page 275
TBM-2 Connections and Ratings Style Y connections Electrical connections: OCC-1 Installation Instructions For Style Z wiring TBM-2 Wiring in an Expander Enclosure 4 - 108 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 276
+24V CZM-1B6 BATTERY POWER CONNECT AT P3 WHEN USING MMB-1 POWER TO OMM +24V NOTIFICATION NOTE: APPLIANCE 24 VDC, 2A MAX. CIRCUIT 2 CABLE 14 AWG MIN. IF SUPPLYING POWER ANALOG LOOP 2 P/N 600-192239 TO MOM, THE WIRING CANNOT LEAVE THE NOTIFICATION ENCLOSURE.
Page 277
24V Remote Power Supply Wiring Diagram firealarmresources.com...
Page 278
VSM-1, VLM-1 and VFM-1 Connections and Ratings Electrical ratings: With an MMB or PSR: Electrical connections: The cables are polarized; do not force them. The cables are polarized; do not force them. NOTE: In a Remote Expander enclosure with a PS-5N7 used instead of an MMB-1/-2 or PSR-1: The cables are polarized;...
XLD-1 Connections and Ratings Electrical ratings: Battery Calculations XLD-1 Input XLD-1 Module Current: 215mA 24V unfiltered, Device Current: 1.1mA per device full wave rectified (Alarm and Supervisory), All wiring must be in accordance with 215mA at 24 VDC (no devices) Article 760 of NEC and the local 1.1mA at 24 VDC (per device) building codes.
ZC1-8B Connections and Ratings Electrical connections: SPEAKER ZONE DECIBEL LOSS for 25.2V RMS, 35W load Gauge Length 14 AWG 16 AWG 18 AWG (feet) (loss in decibels) 1000 SPEAKER ZONE DECIBEL LOSS for 70.7V RMS, 25W load Gauge Length 16 AWG 18 AWG (feet) (loss in decibels)
Page 290
ZC1-8B Connections and Ratings ZC1-8B Speaker Zone Wiring Diagram with One Amplifier as Power Source 4 - 123 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 291
ZC1-8B Connections and Ratings ZC1-8B Strobe Zone Wiring Diagram (25V Only) with a Single DC Power Source 4 - 124 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 292
ZC1-8B Connections and Ratings ZC1-8B Combined Speaker Zone and Strobe Wiring Diagram with a Separate Power Source for Each Input (1, 2, and 3) 4 - 125 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 293
ZC1-8B Connections and Ratings ZC1-8B Speaker Zone Diagram with a Separate 70.7V RMS Power Source for Each Input (1, 2, and 3) 4 - 126 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 303
ZC3-4AB Connections and Ratings SPEAKER ZONE DECIBEL LOSS SPEAKER ZONE DECIBEL LOSS for 25.2V RMS, 35W load for 70.7V RMS, 25W load Gauge Gauge Length Length 14 AWG 16 AWG 18 AWG 16 AWG 18 AWG (feet) (loss in decibels) (feet) (loss in decibels) 0.04...
Page 304
ZC3-4AB Connections and Ratings ZC3-4AB Speaker Zone Wiring Diagram 4 - 137 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 305
ZC3-4AB Connections and Ratings ZC3-4AB Strobe Zone Wiring Diagram 4 - 138 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 306
ZCT-8B Connections and Ratings Electrical ratings: Electrical connections: Outputs COMPATIBLE TELEPHONE UNITS FT-301 Series Warden's Station End of line resistor: FT-302 Series Warden's Station FJ-303 Jack FJ-304 Jack/Terminal Block 4 - 139 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 307
ZCT-8B Connections and Ratings ZCT-8B Telephone Zone Wiring Diagram 4 - 140 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Appendix B Device Analog Voltages B - 1 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 311
Appendix B B - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 312
Appendix C MXL Battery Calculations Battery backup is a requirement for the system current by 90 and record it at MXL. To determine the size battery that Total AH location. you must use, follow the procedures 5. Multiply the AH Total by 1.3 to listed below.
Page 313
Appendix C NOTES The following modules draw no 24 VDC current and do not need to be included in the battery calculations: OMM-1 OMM-2 MOM-2 MOM-4 MMM-1 PLC-4 TBM-2 TSW-2 1. Use this column for battery size calculations. 2. Power is supplied by a separate UPS.
Page 314
Appendix D MXL Power Supply Load Calculations Each MXL System enclosure requires a power supply. This can be either an MMB-2, PSR-1, PS-5A or PS-5N7. To ensure that the power supply is not overloaded, complete the worksheet on the following page. POWER SUPPLY OUTPUT RATINGS Active 24 VDC Module Active 5 VDC Module...
Page 315
Appendix D The following modules draw no current from either the 5 VDC or 24 VDC power supplies and do not need to be included in these calculations: OMM-1 OMM-2 MOM-2 MOM-4 MMM-1 PAL-1 PIM-2 PLC-4 TBM-2 TSW-2 1. Use this column to calculate total current from 24 VDC supply to make sure it is not...
Appendix E Alarm Verification ð CAUTION Use only detectors which are subjected to air velocities of less than 100 feet per minute with Alarm A____________________B________________________C Verification. Under dynamic air velocity conditions, smoke may be swept from a smoke detector after the Timeð...
Page 317
Appendix E ð Alr_Verify Alr_Confirm CSG-M Program- ming Manual E - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 318
Appendix F Envirolink INTELLIGENT ENVIRONMENTAL COMPENSATION (IEC) Envirolink is an optional feature that Envirolink option where it was formerly permits MXL to compensate automati- applied when this new system powers cally for environmental changes (such up. The Envirolink memory re-initializes, as dirt and dust buildup) in the analog and then MXL begins adjusting the voltage of an I Series photo or ion smoke...
Page 319
Appendix F If a detector with Envirolink (IEC) alarm thresholds as needed by using reports an alarm condition before the stored data. detectors alarm threshold is adjusted, the alarm delays until the alarm thresh- Indicating IEC Trouble Conditions old is adjusted. If the device continues A trouble condition involving the IEC to report an alarm condition once its may be annunciated by the MXL as:...
Page 320
Appendix F NOTE: Automatic detection and Press ENTER when the D is blinking to documentation of the cleaning of a select Det_cleaned. detector by MXL may take as long as The System asks you to type the 1 hour. To avoid this, use the Det module and device numbers.
Page 321
Appendix F F - 4 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Appendix G Latching/Non-Latching Troubles This feature is not available for Networked MXL Systems. When the Latching/Non-Latching (self For NFPA 72 Proprietary systems, the restoring) trouble option is set to YES following criteria must be met if the in the CSG-M, MXL automatically trouble is to be removed from the removes trouble conditions from the trouble queue:...
Page 323
Appendix G G - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 324
Appendix H I I I I I nst alling alling A A A A A S S S S S ecur alling ecur ecur it it it it it y y y y y P P P P P oint ecur oint oint...
Page 325
Appendix H H - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Appendix I Application Specific Detection (ASD) Application Specific Detection (ASD) allows the system designer (and anyone with Control menu access) to program an ILP-2 or FP-11 detectors sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions of the detector's environment (application).
Page 327
Appendix I Testing ASD Devices Since one of the parameters transmit- ted to the detector adjusts the detec- tion algorithm (R-algorithm) to reduce false alarms, it is necessary to defeat ASD (or at least the R-algorithm) when smoke testing ASD devices. The Test ASD_Devices menu option has been supplied for this purpose.
Appendix J Testing Every Year To ensure maximum safety, follow the 1. Check that the System operates as procedure described below. To ensure programmed by CSG-M and in proper and reliable operation, we accordance with specifications. recommend the following inspection and testing schedule: 2.
Page 330
Appendix K MXL Trouble Messages Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 331
Appendix K Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 332
Appendix K Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 333
Appendix K Trouble Message The Probable Cause Is: Response out of window at cal. Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 334
Appendix K Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 335
Appendix K Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 336
Appendix K Trouble Message The Probable Cause Is: NOTE: module not responding Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 337
Appendix K Trouble Message The Probable Cause Is: each Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 338
Appendix K Trouble Message The Probable Cause Is: Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 339
Appendix K Trouble Message The Probable Cause Is: Call Pyrotronics K-10 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 340
Appendix K Trouble Message The Probable Cause Is: trouble causing K-11 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 341
Appendix K Trouble Message The Probable Cause Is: K-12 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Appendix L Power Limited Wiring For power limited wiring refer to the following Installation Instructions: Installation Enclosure Instructions LLM-1 315-093530-2 MME-3 315-094883-2 MLE-6 315-094970-1 MXL-RK1 315-093402-6 PLC-4 315-093312-1 L - 1 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 343
Appendix L L - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 344
Appendix M New Two Stage Alarm For use in Canada only with MXL software version 6.04 and higher Fire Protection Company Name CSG-M Memory=2864 used, 243212 free CONFIG => TWOSTG Other System Flags Sensitivity Adjustments Allowed -----------------> NO Block Alarm and Trouble Acknowledge Allowed -----> YES Multienclosure System --------------------------->...
Page 345
Appendix M Selecting Two Stage Other System Flags tions, System Message, Authorizations Example: New Two Stage Configu- Stage 1 audible Stage 2 audible ration Two Stage Audible - 30 / 120 SPM slash Zone Coding Characteristics The final state NOTE: will always be STEADY no matter what is selected in this menu.
Page 346
Appendix M Fire Protection Company Name CSG-M Memory=2900 used, 316874 free CONFIG => TWOSTG Options, System Message, Authorizations System Message -----------------> ----- CERBERUS Pyrotronics ----- Authorization Code-Level 1 -----> 11111 Authorization Code-Level 2 -----> 22222 Authorization Code-Level 3 -----> 33333 COUNTRY where installed -------->...
Page 347
Appendix M NOTE: must be TWO STAGE CONTROL FUNCTIONS NOTE: Stage 1 Stage 2 Coded Audibles in Input Input Ouput List False False Silent Stage 1 Audible Signal True False For example: 30 SPM, steady or zone coding Stage 2 Audible Signal False True For example: 120 SPM,...
Page 348
Appendix M Sample Two Stage Systems Using Reset Inhibit with Timer Keyswitch Devices Keyswitch Type 1 Basic Two Stage System Keyswitch Type 2 stg1_timer M - 5 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 349
Appendix M Complex Two Stage System RESET_INH SS_INH Any Alarm Trigger (ALL) Any Alarm Trigger (ALL) Reset Inhibit 30 Sec Two Stage Audible Silence True Enable Enable True Start Timer Start Timer Cancel Cancel False Panel Reset Typical RESET INHIBIT Timer Function Typical Signal Silence Inhibit Function Any_keyswch Any alarm...
Page 350
Appendix M For example: For example: NOTE Basic Two Stage System M - 7 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 351
Stg1_ssz1 stg1_flr1 stg1_timer Stg1_timer To input list of flr1_2stg Floor 1 stg1_ssz1, (ANY) alarm pts (ALL) stg1_ssz2, Any Alarm Trigger (ALL) Stg1_to Stg1 stg1_ssz3 Audible First Floor Silence stg2_flr1 Two Stage All Alarms Ackd Stg2 Audible List True Enable (ALL) Stg2_sils Any Alarm (ALL)
Page 352
Glossary Analog Loop Appendix A - Compatible Devices Conventional Zone Appendix A - Compatible Devices CSG-M / Custom Software Generator - MXL FSI / Foreign System Interface IEC / Intelligent Environmental Compensation (Envirolink) MNET NCC / Network Command Center Glossary - 1 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 353
Glossary NFPA 12A, 13, and 2001 NFPA 72 Local System (Protected Premises Fire Alarm System) NFPA 72 Proprietary (Proprietary Supervising Station Fire Alarm System) Pseudo Point Glossary - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 354
Glossary RS-232 RS-485 Network UL 1076 System XNET Glossary - 3 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 356
Index See also See also See also See also Index - 1 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 357
Index Index - 2 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 358
Index See also See also Index - 3 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 359
Index See also See also Index - 4 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 360
Index See also See also See also Index - 5 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 361
Index See also See also See also See also See also See also See also See also See also See also Index - 6 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 362
Index See also Index - 7 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 363
Index Index - 8 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 365
Siemens Building Technologies, Ltd. Siemens Building Technologies, Inc. 50 East Pearce Street 8 Fernwood Road Florham Park, New Jersey 07932 Richmond Hill, Ontario L4B 1B7 CN P/N 315-092036CD-8 Technical Manuals Online! - http://www.tech-man.com firealarmresources.com...
Page 366
CSM-4 is power limited on all terminals. i f r . e r 13. For a list of Compatible Notification Appliances, refer to P/N 315-096363. Siemens Building Technologies, Inc. For Proprietary Burglary Application (1076) use " & & - + , - "...