Checking parameter settings
Read parameters in the safety remote I/O module to check if the parameters are consistent with the set values, according to
the following procedure.
1.
Display the "Parameter Processing of Slave Station" window of the safety remote I/O module to be checked.
2.
Select "Parameter read" in "Method selection". Then, click the [Execution] button.
3.
Visually check read values if the parameters are consistent with the set values.
Safety module validation
Validate safety modules according to the following procedure to make the parameters available with set parameters.
1.
Display the "Command Execution of Slave Station" window of the safety remote I/O module to validate safety module.
2.
Select "Safety module validation" in "Method selection". Then, click the [Execution] button.
3.
Restart the safety remote I/O module according to checking window.