■Calculation example of safety refresh monitoring time on CC-Link IE Field Network
Safety refresh monitoring time is used for calculation of the CC-Link IE Field Network transmission time. The following shows
calculation example of network number 1. According to Page 243 Safety refresh monitoring time on CC-Link IE Field Network,
all calculation formulas in (1) to (4) below must be satisfied.
(1) Safety refresh monitoring time  TMact + (TMpas  2) + (LS  2) - a = 9 + (9  2) + (0.85  2) - (9 - 6) = 12.2 [ms]
(2) Safety refresh monitoring time  (TMact  2)+ TMpas + (LS  2) - c = (9  2) + 9 + (0.85  2) - (8 - 4) = 12.2 [ms]
(3) Safety refresh monitoring time > TMact = 9 [ms]
(4) Safety refresh monitoring time > TMpas = 9 [ms]
TMact: Transmission interval monitoring time for a station set to the active side
TMpas: Transmission interval monitoring time for a station set to the passive side
LS: Link scan time for the CC-Link IE Field Network
a: If a station is set to the active side is RJ71GF11-T2, then a = TMact - b. For other cases, a = 0.
b: Value rounds up the calculation results of the TMact  2 to a multiple of the safety cycle time of the master station.
c: If a station is set to the passive side is either RJ71GF11-T2 or NZ2GFSS2-32D, then c = TMpas - d. For other cases, c = 0.
d: Value rounds up the calculation results of the TMpas  2 to a multiple of the safety cycle time of the local station (if NZ2GFSS2-32D, safety refresh response
processing time)
Set the safety refresh monitoring time to 12.2ms to satisfy all in (1) to (4) above.
The following shows a calculation example for network number 2 and 3. According to Page 243 Safety refresh monitoring time
on CC-Link IE Field Network, all calculation formulas in (1) to (4) below must be satisfied.
(1) Safety refresh monitoring time  TMact + (TMpas  2) + (LS  2) - a = 9 + (8  2) + (0.78  2) - (9 - 6) = 11.56  11.6 [ms]
(2) Safety refresh monitoring time  (TMact  2) + TMpas + (LS  2) - c = (9  2) + 8 + (0.78  2)- (8 - 4) = 10.06  10.1 [ms]
(3) Safety refresh monitoring time > TMact = 9 [ms]
(4) Safety refresh monitoring time > TMpas = 8 [ms]
TMact: Transmission interval monitoring time for a station set to the active side
TMpas: Transmission interval monitoring time for a station set to the passive side
LS: Link scan time for the CC-Link IE Field Network
a: If a station is set to the active side is RJ71GF11-T2, then a = TMact - b. For other cases, a = 0.
b: Value rounds up the calculation results of the TMact  2 to a multiple of the safety cycle time of the master station.
c: If a station is set to the passive side is either RJ71GF11-T2 or NZ2GFSS2-32D, then c = TMpas - d. For other cases, c = 0.
d: Value rounds up the calculation results of the TMpas  2 to a multiple of the safety cycle time of the local station (if NZ2GFSS2-32D, safety refresh response
processing time)
Therefore, the safety refresh monitoring time shall be set to: 11.6ms.
■Calculation example of the safety data transmission time (maximum value)
The safety data transmission time (maximum value) is a transmission time of the CC Link IE Field Network from safety input
to safety output.
Safety data transmission time (maximum value) = ( SCcpu  3) + (SRref  4.5) +  RM + SRin + SRout + ( n  2) = (3 + 3)
 3 + (2  4.5) + (12.2 + 11.6 + 11.6) + 1.4 + 0.4 + (1.7 + 1.6 + 1.6)  2 = 74.0
SCcpu: Total value of the safety cycle time of the Safety CPU on the safety path (sum total of safety cycle time of the Safety CPU (1) and Safety CPU (2))
SRref: Safety remote station refresh response processing time
RM: Safety refresh monitoring time of the safety communications on the safety path ( Page 246 Calculation example of safety refresh monitoring time on
CC-Link IE Field Network)
SRin: Input response time of the safety remote I/O module
SRout: Output response time of the safety remote I/O module
n: This shall be 1.8, since it is (1) or (2) below, whichever smaller.
(1) RM - TMmst - (TMoth  2) + a = 12.2 - 9 - (9  2) + (9 - 6) = 1.7
(2) RM - (TMmst  2) - TMoth + c = 12.2 - (9  2) - 9 + (9 - 6) = 1.7
TMmst: transmission interval monitoring time of master station ( Page 244 Calculation example of CC-Link IE Field Network transmission time)
TMoth: transmission interval monitoring time of the local station or remote device station ( Page 244 Calculation example of CC-Link IE Field Network
transmission time)
a: If a station set to active side is the RJ71GF11-T2, then a = TMmst - b. For other cases, a = 0.
b: Value rounds up the calculation results of the TMmst  2
c: If a station set to passive side is either the RJ71GF11-T2 or NZ2GFSS2-32D, then c = TMoth - d For other cases, c = 0.
d: Value rounds up the calculation results of the TMoth  2 to a multiple of the safety cycle time of the local station (if NZ2GFSS2-32D, safety refresh response
processing time)
Calculation example of the maximum value of the safety response time
The following shows a calculation example for safety response time (maximum value)
Safety response time (maximum value) = DT1 + DT2 + Safety data transmission time = DT1 + DT2 + 74.0 [ms]
APPX
246
Appendix 2 Calculating Safety Response Time for System Connected to Multiple Safety CPUs