Mitsubishi Electric MELSEC iQ-R Series Safety Manual page 209

Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Ext. module 1_Wiring selection of output Y2 to Y7
Ext. module 1_Output dark test execution setting Y0
Ext. module 1_Output dark test execution setting Y1
Ext. module 1_Output dark test execution setting Y2 to Y7
Ext. module 1_Output dark test pulse OFF time Y0
Ext. module 1_Output dark test pulse OFF time Y1
Ext. module 1_Output dark test pulse OFF time Y2 to Y7
Ext. module 1_Number of pulse output for output dark test
*1 Adjust the values of input response time, input dark test pulse off time, and output dark test pulse off time according to the installation
environment and wiring length.
*2 Set double input discrepancy detection time to 100ms for mechanical switches and 20ms for sensor inputs as standard.
*3 For details on setting range, refer to the following.
 CC-Link IE Field Network Remote I/O Module (With Safety Functions) User's Manual
*4 Always set the parameters like this for this case example.
*3
Setting details
SR_M2IO1
*4
Not used
*4
Perform
*4
Perform
*4
Do not perform
*1
1ms
*1
1ms
*1
1ms
1 time
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected
SR_M3IO1
SR_M4IO1
*4
Not used
Not used
*4
Perform
Perform
*4
Perform
Perform
*4
Do not perform
Do not perform
1ms
1ms
1ms
1ms
1ms
1ms
1 time
1 time
*4
*4
*4
*4
5
207