ABB FSM4000-SE41F Operating Instruction page 79

Electromagnetic flowmeter
Hide thumbs Also See for FSM4000-SE41F:
Table of Contents

Advertisement

Submenu/parameter
Simulation Mode
Off
Simulation Value
0.0 %
Submenu
Diagnostics
Diagnostics
Manual
Submenu
Diag. Interval
Submenu
Alarm Settings
D184B140U02
Value range
Off
On
Numerical entry
-130 % - +130 %
Start?
Yes, exit via C/CE
Yes → Enter
Cycle Time
Manual; 10 s; 60 s;
10 min; 60 min; 6 h;
Manual
12 h; 24 h; 7 d
Submenu
Alarm Coil Voltage
Min. value
0 ... 150
1.0 V
Max. value
0 ... 150
150 V
Message
Off, warning, error
Off
Comment
On/Off function for Simulation mode. Before operation
with flow, a flowrate can be simulated. The output values
correspond to the simulated flowrate entered. The
information ** Q Simulation** is displayed in the lower line
of the display. After completing the simulation, change the
parameter in the Simulation Mode menu to "Off".
Select the simulation value for the display and outputs.
Current and pulse output follow the flowrate value.
Menu available only if the required hardware is available.
Menu is displayed only with "Manual" diagnostic interval.
Manually start manual diagnostic. The value is displayed
after a delay of 30 s.
Select the time interval between the individual diagnostic
measurements. For the values for Coil Resistance, Coil
Temperature, Insulation Resistance, and Magnetic
Linearity, however, there are minimum measurement
intervals for technical reasons related to the
measurement:
60 seconds for Coil Resistance and Coil Temperature
5 minutes for Magnetic Linearity
10 minutes for measurement of Insulation Resistance
These times are not undershot independently of the
configured diagnostic cyclic.
In this menu you can set minimum and maximum values
for each measurement value. Depending on the selected
configuration, you can select for no message, a warning,
or an error message to be displayed, if the value falls
below or exceeds this threshold.
Set the time-out limits and alarm behavior for values over
or under the coil AC voltage.
Lower range limit for alarm
Upper range limit for alarm
Defines the alarm behavior
FSM4000
Parameterization
79