ABB FSM4000-SE41F Operating Instruction page 82

Electromagnetic flowmeter
Hide thumbs Also See for FSM4000-SE41F:
Table of Contents

Advertisement

Parameterization
Submenu/parameter
82
Value range
Submenu
Alarm Elec Bal
Min. value
100 ... 300
0.0 %
Max. value
100 ... 300
300.0 %
Message
Off, warning, error
Off
Submenu
Alarm Mag Lin
Min. value
0 ... 100
0.0 %
Max. value
0 ... 100
100.0 %
Message
Off, warning, error
Off
Submenu
Alarm SNR
Min. value
0 ... 100
0.0 %
Max. value
0 ... 100
100.0 %
Message
Off, warning, error
Off
Comment
Set the time-out limits and alarm behavior for values over
or under the electrode balance.
The electrode balance is calculated as the ratio between
the electrode AC voltages E1/E2. This value is displayed
in [%]. If the electrode voltage E2 is larger than E1, the
value is assigned a minus sign and the ratio E2/E1 is
displayed.
Lower range limit for alarm.
Upper range limit for alarm.
Defines the alarm behavior.
Note: To properly display the electrode voltage, the
electrode zero must be adjusted. For additional
information, see "Submenu Adjustment" on page 85.
Set the time-out limits and alarm behavior for values over
or under the magnetic linearity.
Lower range limit for alarm.
Upper range limit for alarm.
Defines the alarm behavior.
Note: If magnetic linearity is being measured (at least
every 5 minutes), the most recently acquired flowrate
during the measurement is retained (approx. 2 s).
Set the time-out limits and alarm behavior for values over
or under the signal-to-noise ratio.
Lower range limit for alarm.
Upper range limit for alarm.
Defines the alarm behavior.
FSM4000