ABB FSM4000-SE41F Operating Instruction page 72

Electromagnetic flowmeter
Hide thumbs Also See for FSM4000-SE41F:
Table of Contents

Advertisement

Parameterization
Submenu/parameter
1st line
PID Trk_Value
1st line
TB VolF GOOD0
1st line
AI1 Auto GOOD0
2nd line
Q [percent]
3rd line
Q [percent]
4th line
Q [percent]
Contrast
Submenu
Alarm
Min. Alarm
0 %
Max. Alarm
100 %
Submenu
Totalizer
Overflow → F
0
72
Value range
Comment
Displays the value or status of the parameter Trk_Val for
the function block PID.
Example: The status is displayed in plain text format, the
substatus in numeric form after the status.
Displays the current mode for the function blocks.
Similar to display of
Select the 2nd display line
1st line
Similar to display of
Option unavailable if 1 big, 1 small is selected for the
1st line
display mode
Similar to display of
Option unavailable if 1 big, 1 small is selected for the
1st line
display mode
Set the contrast for the display to adjust to local
conditions, STEP = darker; DATA = lighter.
i
Important:
Adjust the contrast so that the display remains readable.
Numeric entry
Range for the Min. Alarm 0% – Max. Alarm of configured
flow range. Configurable in 1% increments, 1% switching
0% – Max. Alarm
hysteresis.
Numeric entry
Range for the Max. Alarm Min. Alarm – 103% of
configured flow range. Configurable in 1% increments,
Min. Alarm – 103%
1% switching hysteresis.
The totalizer function is set automatically in the
"Operating mode" submenu. Standard operating mode =
standard totalizer function, Piston pump mode = Totalizer
function Diff. totalizer.
Standard = For the standard totalizer function, the
counting pulse for forward and reverse flow is registered
on two separate totalizers. If Forward is selected as flow
direction, only the forwards totalizer counts. Difference
totalizer = in the totalizer function Difference totalizer a
single totalizer is used for both flow directions. For the
forward flow direction the totalizer adds the pulses while
in the reverse flow direction they are subtracted. If the
totalizer value is negative, i.e., the reverse flow totals are
greater than the forward flow totals, the flow direction
indicator in the display changes from "F" to "R". The pulse
output (active or passive) is not affected by this switch.
Display only
Overflow counter max. 65535. 1 overflow = pulse totalizer
of 9,999,999 units. Resets the display status and
increments the overflow counter by one. Overflow
example:
Overflow 012 12 x 10.000.000 units = 120.000.000 units
+ 23.455 current totalizer value results in a total of
120.023.455 units
FSM4000
D184B140U02