Parameterization
Submenu/parameter
Unit Qmax
l/s
Submenu
Prog. Unit
Submenu
System data
Submenu
Converter
Submenu
Data 50 Hz
64
Value range
l/s; l/min; l/h; m
m
usgps; usgpm;
usgph; usmgd; igps;
igpm; igph; igpd;
bbl/s; bbl/m; bbl/h;
bbl/d; g/s; g/min, g/h;
kg/s;kg/min; kg/h;
kg/d; t/min; t/h; t/d;
lb/s; lb/min; lb/h; lb/d;
ml/s, ml/min
Prog. Unit/s
Prog. Unit/min
Prog. Unit/h
Prog. Unit/d
Text entry
Unit name
kgal
Numeric entry
Unit factor
3785.1
Without density
Prog. Unit
With density
without density
Numeric entry
Density
1 g/cm 3
View only
Channel
-123 µs
View only
Zero
0 %
Span → V
View only
91 %
Span ← R
View only
-91 %
Comment
3
Select the unit for volume and mass flow. This unit refers
/s;
to Qmax DN, Qmax and the instantaneous status, if these
3
3
3
/min; m
/h; m
/d;
are displayed in engineering units.
For PROFIBUS PA, the following units are also displayed:
3
en ft
/s; ft
For PROFIBUS PA, the following units are not displayed:
Prog. unit and ml/s.
1)
kgal = Factory setting
1)
1)
1)
1)
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Four character name for the user programmable unit.
kgal = Factory setting.
Reference factor for the user-defined units based on
liters; default value in kgal units (factory setting).
Unit for mass (with density) or volume (without density).
Density range 0.1 ... -5 g/cm 3 . Mass flowrate for display
and totalization. The density is only considered when
mass flow units are and/or totalizer mass units are
selected.
This menu does not appear with an excitation frequency
of 60 Hz or 70 Hz.
Adjustment value for Channel can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Adjustment value for Zero can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Adjustment value for Span Forward can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Adjustment value for Span Reverse can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
FSM4000
3
3
3
/min; ft
/h; ft
/d.
D184B140U02