Parameterization
Submenu/parameter
Cal-fact 10m/s
50 m 3 /h
Qmax
50 m 3 /h
Damping [1\xE0]
1 sec
Low flow cut off
1.0 %
Submenu
Detector e. pipe
Detector e. pipe
Off
DEP Mode
Standard
68
Value range
Comment
View only
Display the max. possible flow range. Automatically
selected based on size.
Numeric entry
Flow range end value for forward and reverse flow. Flow
range end value configurable from 0.5 ... 10 m/s.
Numeric entry
Response time, after 1τ the value displayed has reached
63% of its end value (after 5τ). The following values can
be selected, operating mode: Standard 0.2 ... 20 s,
fast/piston pump 0.07 ... 20 s.
Numeric entry
Applicable for display and all outputs. The switching limit
0 ... 10% of Qmax
for the low flow cutoff has a built-in hysteresis of 0.1%.
i
Important:
The meter pipe must be completely filled to ensure proper
measurement. The function "Detector empty pipe" can be
used to continuously monitor this condition. If the fluid
level drops below the electrode level, all outputs can be
automatically set to zero. This ensures false pulses or
incorrect displays are avoided when the meter pipe is
empty. In addition to the message in the display, this
condition can be reported via the switch contact output. If
the meter pipe is filled, the error message "empty pipe" is
turned off and the meter returns to normal operation.
Off
Turn on/off the "Detector empty pipe" function. Not
configurable for sizes:
On
1 mm 1/25 in
1,5 mm 1/17 in
2 mm
3 mm
4 mm
6 mm
8 mm
i
Important:
The "empty pipe" function is not available for flowmeter
primaries with preamplifiers. The menu is hidden.
Select the function "Standard" or "New Adjust". The
Standard
transmitter is shipped in "Standard" DEP mode. For most
New Adjust
applications, the DEP function will run properly in
"Standard" mode. For all other applications, the DEP
mode "New Adjust" should be selected. The adjustment
can be made with a full and/or empty meter pipe.
Not displayed, if DEP is switched off.
FSM4000
1/12 in
1/10 in
5/32 in
1/4 in
5/16 in
D184B140U02