ABB FSM4000-SE41F Operating Instruction page 75

Electromagnetic flowmeter
Hide thumbs Also See for FSM4000-SE41F:
Table of Contents

Advertisement

Submenu/parameter
Submenu
Label
Curr. Variant
Active pulse without
HART
Sensor TAG
„----------------------"
Transmitter TAG
„----------------------"
Submenu
Interface
Communication
None
Device address
0
HART TAG
"HART TAG"
HART descriptor
"HART descriptor"
D184B140U02
Value range
Comment
Display only
Displays the pulse output and communication
configuration for the shipped model.
Active pulse without
HART
Active pulse with
HART
Passive pulse without
HART
Passive pulse with
HART
PROFIBUS PA
FOUNDATION
Fieldbus FF
Variant error
User-defined text
A TAG number to identify the flowmeter sensor, max. 32-
character limit.
User-defined text
A TAG number to identify the transmitter, max. 32-
character limit.
None
1. HART communication
HART
Set the HART communication to ON or OFF. When HART
communication is not required, Current Output ranges 0-
20, 0-10, 2-10 mA can be selected. For HART
communication, the current output is always
4 - 20 mA.
No selection available for standard devices (without
HART hardware).
Numerical entry
For devices with HART protocol, an address between 0 ...
15 can be selected. If the address entered is 0, the
0 ... 15
current output varies with the flowrate in the range of 4-20
mA. If multiple devices are connected to the bus and an
address between 1 and 15 is assigned, the transmitter
runs in multidrop mode. The current output value then
remains frozen at 4 mA. In this case, the output values
can only be read using HART communication. Warning
11 is displayed.
No entry for standard devices (without HART hardware).
User-defined text
Unique identifier for unit using HART TAG number. Max.
8-character TAG number (PCKASCII string). Only capital
letters are recognized, no special characters can be used.
No entry for standard devices (without HART hardware).
User-defined text
Description max. 16-character (PCKASCII string). Only
capital letters are recognized, no special characters can
be used.
No entry for standard devices (without HART hardware).
FSM4000
Parameterization
75