2. Switch on the supply power; the model number of the transmitter and the current software
version are displayed.
The flowmeter sensor and system data from the external FRAM are imported:
a) The following information is displayed:
-
When replacing the transmitter all flowmeter sensor and measuring point parameters are
loaded into the replacement transmitter. After successful data transfer, the "Warning 7"
message is deleted after approx. 30 sec.
b) Transmitter and flowmeter sensor are put into operation again (e.g., after a power failure):
No warning is displayed; the transmitter runs automatically with the data from the internal
and external FRAM.
c) Only the transmitter is replaced; order numbers are not identical. The external flowmeter
-
d) If the order number, unit number, Cs, Cz and size are identical (e.g., if the transmitter
-
If the external data cannot be loaded in scenarios a) to d), the program attempts to repair the
defective data. The following messages may be displayed:
-
-
Both messages can be displayed simultaneously.
If this occurs, the following error is displayed:
-
-
3. Check whether the language, display format, flow ranges, alarm settings and flowmeter
sensor data match the values listed on the name plate for the flowmeter sensor. If
parameters are subsequently changed, these are stored automatically in the external FRAM.
4. The measuring system is ready for operation.
D184B140U02
Warning 7 - Primary data loaded.
sensor and system data is imported. The following message is displayed:
Warning 7 - Primary data loaded.
from the delivery is used with identical configuration data), the process data is imported
from the internal to external FRAM. The flowmeter sensor data continues to be imported
from the external to internal FRAM. The following message is displayed:
Warning 8b – (Update external FRAM).
Warning 8a – (Update internal data) - for data flow direction external → internal
Warning 8b – (Update external data) - for data flow direction internal → external
Error C - for the external FRAM, the FRAM must be replaced
Error 5 - for the internal FRAM, the transmitter starts automatically with default values. In
some instances, it may be possible to eliminate this error by turning the supply power off
and on. If this does not work, the transmitter must be replaced.
FSM4000
Maintenance / Repair
107