Additional functions
RPM
1500
300
t
Start
Stop
The oil pressure alarm (RMI oil) will be enabled during idle run if set to "ON".

7.10.4 Inhibit

The alarms that are deactivated by the inhibit function are inhibited in the usual manner, except for the oil
pressure alarms; RMI oil 6,7 and 8 which are active during "idle run" as well.

7.10.5 Running signal

The running feedback must be activated when the genset is running in idle mode.

7.10.6 Idle speed flowcharts

The flowcharts illustrate the starting and stopping of the genset by use of the inputs "temp control" and "low
speed".