2.3.2
I/O signals when the double setting is set in CC-
Link Ver.2 (Pr.544 = "112")
The number of device points available in CC-Link communication are 32 input (RX) points (12 points for the PLC function), 32
output (RY) points (12 points for the PLC function), 4 remote register (RWr) points, and 4 remote register (RWw) points.
Remote I/O
PLC function
Remote output
device number
device number
X30
RYn0
X31
RYn1
X32
RYn2
X33
RYn3
X34
RYn4
X35
RYn5
X36
RYn6
X37
RYn7
X38
RYn8
X39
RYn9
X3A
RYnA
X3B
RYnB
RYnC
RYnD
RYnE
Signal name
Forward rotation
command
Reverse rotation
command
High-speed operation
command
(Terminal RH function)

Middle-speed operation
command
(Terminal RM function)

Low-speed operation
command
(Terminal RL function)

JOG operation
command
(Terminal JOG function)

Second function
selection
(Terminal RT function)

Current input selection
(Terminal AU function)

Selection of automatic
restart after
instantaneous power
failure
(Terminal CS function)
,


Output stop
Start self-holding
selection
(Terminal STP (STOP)
function)

Reset
(Terminal RES function)

Monitor command
Frequency setting
command (RAM)
Frequency setting
command
(RAM, EEPROM)
CC-Link I/O specifications
PLC function
Remote input
device number
device number
Y30
RXn0
Y31
RXn1
Y32
RXn2
Y33
RXn3
Y34
RXn4
Y35
RXn5
Y36
RXn6
Y37
RXn7
Y38
RXn8
Y39
RXn9
Y3A
RXnA
Y3B
RXnB
RXnC
RXnD
RXnE
CC-Link communication
Signal name
Forward rotating
Reverse rotating
Running
(Terminal RUN function)

Up to frequency
(Terminal SU function)

Overload alarm
(Terminal OL function)

Instantaneous power
failure
(Terminal IPF function)

Frequency detection
(Terminal FU function)

Fault
(Terminal ABC1 function)

(Terminal ABC2 function)

Pr.313 assignment
function (DO0)

Pr.314 assignment
function (DO1)

Pr.315 assignment
function (DO2)

Monitoring
Frequency setting
completion (RAM)
Frequency setting
completion (RAM,
EEPROM)
61
2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F800

Table of Contents