Explanation of devices
Accuracy
The value obtained by the END instruction is added to the current value when the OUT T instruction is executed. The
current value is not updated while the timer coil is off even if the OUT T instruction is executed.
Program
10ms counting
Count at
execution of the
END instruction
Current value
of T0
External input
to X0
Inverter X0
Coil of T0
Contact of T0
Scan time
Accuracy of the timer response that is from reading input (X) to output the data are up to
"2-scan time + timer limit setting".
90
Sequence program
Timer limit setting=10ms, Setting value of T0=8 (10ms 8=80ms), Scan time=25ms
END
END
processing
processing
2
3
1
2
1
2
0+2=2
ON
OFF
ON
OFF
ON
OFF
OFF
25ms
25ms
Timing when the coil of the timer turns on
Input reading timing
END
END
processing
processing
1
2
1
2
3
1
3
2
3
2+3=5
5+2=7
25ms
25ms
25ms
Accuracy from when the coil of the timer turns on until
when the contact of the timer turns on
- (1 scan time + timer limit setting) to (1 scan time)
K8
X0
T0
END
END
processing
processing
2
1
2
3
2
3
7+3=
ON
25ms