Inverter Parameter Access Error (Sd1150); Inverter Status (Sd1151) - Mitsubishi Electric A800 Programming Manual

800 series, plc function
Hide thumbs Also See for A800:
Table of Contents

Advertisement

Special registers to monitor and control inverter status
1.9.5

Inverter parameter access error (SD1150)

Device
number
SD1150
Inverter parameter access error
When an out-of-range setting value is written to a parameter or an out-of-range frequency is set using sequence programs, or
when writing is attempted while writing is disabled, a write error occurs and an error code is stored in SD1150.
<Parameters>
Parameter number + H8000 is stored to SD1150.
Example) If an error occurs when Pr.0 Torque boost is written, H8000 (H0 + H8000) is stored to SD1150.
If an error occurs when Pr.10 DC injection brake operation frequency is written, H800A is stored to SD1150.
<Operation mode, setting frequency, batch clear of fault records, and all parameter clear>
HFFFF is stored to SD1150. (The initial values is "0".)
POINT
POINT
• The error code stored after the error occurrence will be cleared by writing "0" in SD1150. (The error code is retained until "0"
is written in SD1150.)
1.9.6

Inverter status (SD1151)

Device
number
SD1151
Inverter status
Operating status of the inverter is stored.
Each bit is set according to the status of the inverter.
44
PLC Function
Name
Always accessible
Name
Always accessible
b15
b8 b7
b4 b3
Terminal SO status
Data access condition
Data access condition
b0
0:OFF
1:ON
Inverter running(RUN)
Forward running
Reverse running
Up to frequency(SU)
Overload alarm(OL)
Instantaneous power failure
/undervoltage(IPF)
Output frequency
detection(FU)
Fault output(ALM)
Alarm output(LF)