1.9.7

User-defined error (SD1214)

By setting the values "16 to 20" in SD1214, alarms for the inverter can be created. When an alarm occurs, the inverter stops.
Values other than "16 to 20" are invalid. Furthermore, this function is disabled when Pr.414 = "0".
The created alarms are recognized as E.16 to E.20 by the inverter.
1.9.8

Monitor setting selection (SD1215 to SD1218)

The content of SD1216 to SD1218 can be displayed on the operation panel or the parameter unit.
Use SD1215 to set the decimal point display for displaying the content of SD1216 to SD1218 on the operation panel or the
parameter unit.
To display the content of SD1216 to SD1218 on the operation panel or the parameter unit, set "40 to 42" in Pr.774 to Pr.776.
Monitor
Device
description
SD1216
User monitor 1
SD1217
User monitor 2
SD1218
User monitor 3
To display the monitors set in SD1216 to SD1218 to decimal places, set SD1215 as follows.
<Setting of SD1215>
b15

Ignore bits other than those above.
<Decimal point display setting>
bn + 1
bn
0
0
1 increment (no decimals)
0
1
0.1 increment
1
0
0.01 increment
1
1
0.001 increment
Setting example:
1. To display SD1216 without decimals
• Set H0000 in SD1215.
• Set "40" in Pr.774.
2. To display SD1216 in 0.1 increment, and SD1218 in 0.001 increment.
• Set H3100 in SD1215.
• Set "40" in Pr.774 and "42" in Pr.776.
POINT
POINT
• For monitoring SD1216 to SD1218 on the LCD operation panel or the parameter unit, the monitor names and
units can be set in SD1216 to SD1218 by using G.PRR, GP.PRR, or UMSG instruction (refer to
For details of Pr.774 to Pr.776, refer to the Instruction Manual (Detailed) of the inverter.
Special registers to monitor and control inverter status
Pr.774 to Pr.776 setting
40
41
42
b12 b11
b8 b7
b4 b3
b0
Select the displayed decimal point for the SD1216 monitor.
Select the displayed decimal point for the SD1217 monitor.
Select the displayed decimal point for the SD1218 monitor.
Increment
page
195).
45
PLC Function