Security - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
Table 2–2: OTHER DEVICE FUNCTIONS
FUNCTION
Current metering: true RMS, phasors,
symmetrical
Data logger
Digital counters (8)
Digital elements (48)
Disconnect switches (24)
DNP 3.0 or IEC 60870-5-104 protocol
The following security features are available:
Password security — Basic security present in the default offering of the product
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
a) ENERVISTA SECURITY
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a substa-
tion and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security management
system is disabled by default to allow the administrator direct access to the EnerVista software after installation. It is recom-
mended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
b) PASSWORD SECURITY
Password security is a basic security feature present in the default offering of the product.
Two levels of password security are provided: command and setting.
The following operations are under command password supervision:
Changing the state of virtual inputs
Clearing the event records
Clearing the oscillography records
Changing the date and time
Clearing the data logger
Clearing the user-programmable pushbutton states
The following operations are under setting password supervision:
Changing any setting
Test mode operation
GE Multilin
FUNCTION
Non-volatile latches
Non-volatile selector switch
Oscillography
Power metering
Power factor metering
Setting groups (6)
Time and date
C70 Capacitor Bank Protection and Control System
2.1 INTRODUCTION
FUNCTION
Virtual inputs (64)
Virtual outputs (96)
Voltage metering: true RMS, phasors,
symmetrical
Voltage regulator
VT fuse failure

2.1.2 SECURITY

2
2-3

Advertisement

Table of Contents
loading