5 SETTINGS
The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica-
tions capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering
section of chapter 2 for additional details.
Use independent ports for IEC 61850 communication and take care when configuring the settings,
else loss of protection or misoperation of the relay can result.
The C70 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported
over two protocol stacks: TCP/IP over Ethernet. The C70 operates as an IEC 61850 server. The Remote inputs and outputs
section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
The GSSE/GOOSE configuration main menu is divided into two areas: transmission and reception.
PATH: SETTINGS
PRODUCT SETUP
 GSSE / GOOSE
 CONFIGURATION
MESSAGE
The main transmission menu is shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
 TRANSMISSION
MESSAGE
MESSAGE
MESSAGE
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
GENERAL
 GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP

TRANSMISSION
GSEE
 GSSE
MESSAGE
MESSAGE
GE Multilin


COMMUNICATIONS
IEC 61850 PROTOCOL
 TRANSMISSION
 RECEPTION


COMMUNICATIONS
IEC 61850 PROTOCOL
 GENERAL
 GSSE
 FIXED GOOSE
 CONFIGURABLE
 GOOSE


COMMUNICATIONS
IEC 61850 PROTOCOL
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed C70 GOOSE, and configurable GOOSE.


COMMUNICATIONS
IEC 61850 PROTOCOL
GSSE FUNCTION:
Enabled
GSSE ID:
GSSEOut
DESTINATION MAC:
000000000000
C70 Capacitor Bank Protection and Control System
5.2 PRODUCT SETUP
GSSE/GOOSE CONFIGURATION
GSSE/GOOSE CONFIGURATION
GSSE/GOOSE CONFIGURATION
Range: 1 to 60 s in steps of 1
GSSE/GOOSE CONFIGURATION
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address