5.2 PRODUCT SETUP
5.2PRODUCT SETUP
a) SECURITY OVERVIEW
The following security features are available:
•
Password security — Basic security present in the default offering of the product
•
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
•
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
b) LOST PASSWORD
If all passwords are lost, recovery is possible by resetting the unit to default values.
To reset the unit after a lost password:
1.
Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2.
Enter the reset code on the front panel, under Commands > Commands Relay Maintenance > Service Command.
3.
Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
section in the first chapter.
c) PASSWORD REQUIREMENTS
For password security and CyberSentry security, a user account requires an alpha-numeric password that meets the follow-
5
ing requirements:
•
Password is case-sensitive
•
Password cannot contain the user account name or parts of the user account that exceed two consecutive characters
•
Password must be 6 to 20 characters in length
•
Password must contain characters from three of the following four categories:
- English uppercase characters (A through Z)
- English lowercase characters (a through z)
- Base 10 digits (0 through 9)
- Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
d) PASSWORD SECURITY
PATH: SETTINGS
PRODUCT SETUP
SECURITY
The C70 supports password entry from a local or remote connection.
5-8
SECURITY
ACCESS LEVEL:
Restricted
CHANGE LOCAL
MESSAGE
PASSWORDS
ACCESS
MESSAGE
SUPERVISION
DUAL PERMISSION
MESSAGE
SECURITY ACCESS
PASSWORD ACCESS
MESSAGE
EVENTS: Disabled
C70 Capacitor Bank Protection and Control System
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
See page 5–9.
See page 5–10.
See page 5–11.
Range: Disabled, Enabled
5 SETTINGS
5.2.1 SECURITY
GE Multilin