5.6 GROUPED ELEMENTS
a) MAIN MENU

PATH: SETTINGS
GROUPED ELEMENTS
 VOLTAGE ELEMENTS
5
These protection elements can be used for a variety of applications such as:
Undervoltage Protection: For voltage sensitive loads, such as induction motors, a drop in voltage increases the
drawn current which may cause dangerous overheating in the motor. The undervoltage protection feature can be used
5-176
SETTING GROUP 1(6)
 PHASE
 UNDERVOLTAGE1
 PHASE
MESSAGE
 UNDERVOLTAGE2
 PHASE
MESSAGE
 OVERVOLTAGE1
 NEUTRAL OV1
MESSAGE
 NEUTRAL OV2
MESSAGE
 NEUTRAL OV3
MESSAGE
 NEG SEQ OV1
MESSAGE
 NEG SEQ OV2
MESSAGE
 NEG SEQ OV3
MESSAGE
 AUXILIARY OV1
MESSAGE
 AUXILIARY OV2
MESSAGE
 AUXILIARY OV3
MESSAGE
 VOLTAGE
MESSAGE
 DIFFERENTIAL 1
 VOLTAGE
MESSAGE
 DIFFERENTIAL 2
 VOLTAGE
MESSAGE
 DIFFERENTIAL 3
 BANK
MESSAGE
 OVERVOLTAGE
 NEUTRAL VOLTAGE
MESSAGE
 UNBALANCE 1
 NEUTRAL VOLTAGE
MESSAGE
 UNBALANCE 2
 NEUTRAL VOLTAGE
MESSAGE
 UNBALANCE 3
C70 Capacitor Bank Protection and Control System


VOLTAGE ELEMENTS

See page 5–178.
See page 5–178.
See page 5–179.
See page 5–180.
See page 5–180.
See page 5–180.
See page 5–181.
See page 5–181.
See page 5–181.
See page 5–182.
See page 5–182.
See page 5–182.
See page 5–183.
See page 5–183.
See page 5–183.
See page 5–186.
See page 5–190.
See page 5–190.
See page 5–190.
5 SETTINGS
5.6.8 VOLTAGE ELEMENTS
GE Multilin

Advertisement

Table of Contents
loading