APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 61)
ADDR
REGISTER NAME
4508
...Repeated for VT Bank 2
4510
...Repeated for VT Bank 3
4518
...Repeated for VT Bank 4
4520
...Repeated for VT Bank 5
4528
...Repeated for VT Bank 6
Source Settings (Read/Write Setting) (6 modules)
4580
Source 1 Name
4583
Source 1 Phase CT
4584
Source 1 Ground CT
4585
Source 1 Phase VT
4586
Source 1 Auxiliary VT
4587
...Repeated for Source 2
458E
...Repeated for Source 3
4595
...Repeated for Source 4
459C
...Repeated for Source 5
45A3
...Repeated for Source 6
Power System (Read/Write Setting)
4600
Nominal Frequency
4601
Phase Rotation
4602
Frequency And Phase Reference
4603
Frequency Tracking Function
Breaker control (read/write settings)
47D0
Breaker 1 function
47D1
Breaker 1 name
47D4
Breaker 1 mode
47D5
Breaker 1 open
47D7
Breaker 1 close
47D9
Breaker 1 phase A / three-pole closed
47DB
Breaker 1 phase B closed
47DD
Breaker 1 phase C closed
47DF
Breaker 1 external alarm
47E1
Breaker 1 alarm delay
47E3
Breaker 1 pushbutton control
47E4
Breaker 1 manual close recall time
47E6
Breaker 1 out of service
47E8
Breaker 1 block open
47EA
Breaker 1 block close
47EC
Breaker 1 phase A / three-pole opened
47EE
Breaker 1 phase B opened
47F0
Breaker 1 phase C opened
47F2
Breaker 1 operate time
47F3
Breaker 1 events
47F4
Reserved
47F5
...Repeated for breaker 2
481A
...Repeated for breaker 3
483F
...Repeated for breaker 4
4864
...Repeated for breaker 5
4889
...Repeated for breaker 6
FlexCurve A (Read/Write Setting)
4910
FlexCurve A (120 items)
FlexCurve B (Read/Write Setting)
4988
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
GE Multilin
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 655535
0 to 655535
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 1
---
---
0 to 63
---
1
0 to 63
---
1
0 to 63
---
1
0 to 63
---
1
25 to 60
Hz
1
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0 to 1
---
1
---
---
---
0 to 1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
s
0.001
0 to 1
---
1
s
0.001
---
1
---
1
---
1
---
1
---
1
---
1
s
0.001
0 to 1
---
1
0 to 65535
s
1
ms
1
ms
1
0 to 65535
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F206
"SRC 1"
F400
0
F400
0
F400
0
F400
0
F001
60
F106
0 (ABC)
F167
0 (SRC 1)
F102
1 (Enabled)
F102
0 (Disabled)
F206
"Bkr 1"
F157
0 (3-Pole)
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F003
0
F102
0 (Disabled)
F003
0
F300
0
F300
0
F300
0
F300
0
F300
0
F300
0
F001
70
F102
0 (Disabled)
F001
0
F011
0
F011
0
F001
0
B-29