GE C70 Instruction Manual page 37

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
There are two types of authentication supported by CyberSentry that can be used to access the UR device:
Device Authentication (local UR device authenticates)
Server Authentication (RADIUS server authenticates)
The EnerVista software allows access to functionality that is determined by the user role, which comes either from the local
UR device or RADIUS server.
The EnerVista software has a device authentication option on the login screen for accessing the UR device. When the
"Device" button is selected, the UR uses its local authentication database and not the RADIUS server to authenticate the
user. In this case, it uses its built-in roles (Administrator, Engineer, Supervisor, Observer, Operator) as login names and the
associated passwords are stored on the UR device. As such, when using the local accounts, access is not user-attribut-
able.
In cases where user attributable access is required especially to facilitate auditable processes for compliance reasons, use
RADIUS authentication only.
When the "Server" Authentication Type option is selected, the UR uses the RADIUS server and not its local authentication
database to authenticate the user.
No password or security information are displayed in plain text by the EnerVista software or UR device, nor are they ever
transmitted without cryptographic protection.
CYBERSENTRY USER ROLES
CyberSentry user roles (Administrator, Engineer, Operator, Supervisor, Observer) limit the levels of access to various UR
device functions. This means that the EnerVista software allows for access to functionality based on the user's logged in
role.
Example: Observer cannot write any settings.
The table lists the roles that are supported and their corresponding capabilities.
Table 2–3: PERMISSIONS BY USER ROLE FOR CYBERSENTRY
Roles
Device Definition
Settings
|------------ Product Setup
|--------------- Security (CyberSentry)
|--------------- Supervisory
|--------------- Display Properties
Clear relay records
|---------------
(settings)
|--------------- Communications
|--------------- Modbus user map
|--------------- Real Time Clock
|--------------- Oscillography
|--------------- Data Logger
|--------------- Demand
User Programmable
|---------------
LEDs
User Programmable
|---------------
self test
|--------------- Control Pushbuttons
User programmable
|---------------
Pushbuttons
|--------------- Flex states
GE Multilin
Administrator
Complete access
R
RW
see table notes
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
C70 Capacitor Bank Protection and Control System
Engineer
Operator
Complete access
Command
except for
menu
CyberSentry
Security
R
R
R
R
R
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
RW
R
2.1 INTRODUCTION
Supervisor
Observer
Authorizes
Default role
writing
R
R
R
R
see table notes
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
2-5
2

Advertisement

Table of Contents
loading