B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 9 of 61)
ADDR
REGISTER NAME
Security (Read Only)
329F
Supervisor alphanumeric password status
Security (Read Only)
32B4
Engineer alphanumeric password status
Security (Read Only)
32C9
Operator alphanumeric password status
Security (Read Only)
32DE
Observer alphanumeric password status
Security (Read Only)
32E9
Reserved for password settings of future roles (63 items)
B
3328
Security status indicator
Security (Read/Write Setting)
3329
Session Lockout
332A
Session Lockout Period
332B
Load Factory Defaults
332C
Syslog Serve IP Address
332E
Syslog Server Port Number
Security Supervisory (Read/Write Setting)
3331
Device Authentication Enable
3332
Supervisor Role Enable
3333
Lock Relay
3334
Factory Service Mode Enable
3335
Failed Authentication Alarm Enable
3336
Firmware Lock Alarm
3337
Settings Lock Alarm
3338
Bypass Access
3339
Encryption
333A
Serial Inactivity Timeout
Security Command (Read/Write Command)
3350
Operator Logoff
3351
Engineer Logoff
3352
Administrator Logoff
3353
Clear Security Data
Security Reserved Modbus Registers (Read/Write)
3360
Address 0x3360 reserved for serial login (20 items)
3374
Address 0x3374 reserved for serial logout
Security Reserved Modbus Registers (Read Only)
3375
Address 0x3374 reserved for serial logout
Event recorder actual values (read only)
3400
Events Since Last Clear
3402
Number of Available Events
3404
Event Recorder Last Cleared Date
Event recorder commands (read/write)
3406
Event Recorder Clear Command
Neutral current unbalance commands and actual values (read/write unless noted, 3 modules)
3410
Neutral current unbalance automatic setting function
3411
Neutral current unbalance apply magnitude
3412
Neutral current unbalance apply angle
3413
60N apply magnitude actual value (read only)
3415
60N apply angle actual value (read only)
3417
...Repeated for neutral current unbalance 2
341E
...Repeated for neutral current unbalance 3
Neutral voltage unbalance commands and actual values (read/write unless noted, 3 modules)
3430
Neutral voltage unbalance automatic setting function
B-16
0 to 65535
0 to 65535
0 to 9999
0 to 4294967295
0 to 65535
1 to 9999
0 to 9999
0 to 9999
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 0.1500
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
---
1
---
1
0 to 99
---
1
min
1
0 to 1
---
1
---
1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
---
1
---
1
0 to 5
---
1
---
1
---
1
---
1
0 to 1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
---
0.0001
0 to 359
°
1
0 to 2
---
1
APPENDIX B
FORMAT
DEFAULT
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F001
0
F618
0
F001
3
F001
3
F126
0 (No)
F003
0
F001
514
F126
1 (Yes)
F102
0 (Disabled)
F102
0 (Disabled)
F102
0 (Disabled)
F102
1 (Enabled)
F102
1 (Enabled)
F102
1 (Enabled)
F628
0 (Disabled)
F102
1 (Enabled)
F001
1
F126
0 (No)
F126
0 (No)
F126
0 (No)
F126
0 (No)
F001
3
F001
3
F617
3 (Engineer)
F003
0
F003
0
F050
0
F126
0 (No)
F092
0 (Disabled)
F126
0 (No)
F126
0 (No)
F003
0
F003
0
F092
0 (Disabled)