6 ACTUAL VALUES

PATH: ACTUAL VALUES
STATUS
 IEC 61850
 GOOSE UINTEGERS
MESSAGE
MESSAGE
The C70 Capacitor Bank Protection and Control System is provided with optional IEC 61850 communica-
tions capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering
section of chapter 2 for additional details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
STATUS
 COMM STATUS
 REMAINING CONNECT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
These values specify the remaining number of TCP connections still available for each protocol. Every time a connection is
used, the remaining number of connections decrements. When released, the remaining number of connections increments.
If no connection is made over the specific protocol, the number equals the maximum number available for the specific pro-
tocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
Note that the maximum number of PMU TCP connections matches the number of aggregators.
GE Multilin

IEC 61850 GOOSE UINTEGERS
UINT INPUT
1
0
UINT INPUT
2
0
UINT INPUT 16
0

COMM STATUS REMAINING CONNECT
MMS (max 5)
5
MODBUS TCP (max 4)
4
DNP (max 2)
2
IEC-104 (max 2)
2
PMU TCP (max 4)
4
C70 Capacitor Bank Protection and Control System

6.2.16 IEC 61850 GOOSE INTEGERS

6.2.17 REMAINING CONNECTION STATUS
Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 0 to 4
6.2 STATUS
6
6-9