Communications - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 COMMUNICATIONS
5
b) SERIAL PORTS
PATH: SETTINGS
PRODUCT SETUP
 SERIAL PORTS
The C70 is equipped with up to two independent serial communication ports. The faceplate RS232 port is intended for local
use and is fixed at 19200 baud and no parity. The rear COM2 port is RS485. The RS485 port has settings for baud rate and
parity. It is important that these parameters agree with the settings used on the computer or other equipment that is con-
nected to these ports. Any of these ports can be connected to a computer running EnerVista UR Setup. This software can
download and upload setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays
can be daisy-chained and connected to a DCS, PLC, or computer using the RS485 ports.
For the RS485 port, the minimum time before the port transmits after receiving data from a host can be set. This
feature allows operation with hosts which hold the RS485 transmitter active for some time after each transmission.
NOTE
c) ETHERNET NETWORK TOPOLOGY
When using more than one Ethernet port, configure each to belong to a different network or subnet using the IP addresses
and mask, else communication becomes unpredictable when more than one port is configured to the same subnet.
5-26


COMMUNICATIONS

 SERIAL PORTS
 NETWORK
MESSAGE
 ROUTING
MESSAGE
 MODBUS PROTOCOL
MESSAGE
 DNP PROTOCOL
MESSAGE
 DNP / IEC 104
MESSAGE
 POINT LISTS
 IEC 61850 PROTOCOL
MESSAGE
 WEB SERVER
MESSAGE
 HTTP PROTOCOL
 TFTP PROTOCOL
MESSAGE
 IEC 60870-5-104
MESSAGE
 PROTOCOL
 EGD PROTOCOL
MESSAGE

COMMUNICATIONS
RS485 COM2 BAUD
RATE: 19200
RS485 COM2 PARITY:
MESSAGE
None
RS485 COM2 RESPONSE
MESSAGE
MIN TIME:
C70 Capacitor Bank Protection and Control System
See below.
See page 5–29.
See page 5–31.
See page 5–34.
See page 5–34.
See page 5–37.
See page 5–38.
See page 5–53.
See page 5–53.
See page 5–54.
See page 5–55.
SERIAL PORTS
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
0 ms
5 SETTINGS
5.2.4 COMMUNICATIONS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents