GE C70 Instruction Manual page 143

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5 SETTINGS
Security Alarm Settings
SETTING NAME
DESCRIPTION / DETAILS
Failed
A threshold number indicating when an alarm is
Authentications
set off to indicate too many failed authentication
attempts
Firmware lock
A Boolean value indicating if the device can
receive a firmware upgrade. If Yes and a
firmware upgrade attempt is made, the device
alarm activates. If No the device alarm does not
activate. On each firmware upgrade this setting
goes back to the default.
Settings lock
A Boolean value indicating if the device can
accept any settings changes. If Yes and a
settings change attempt is made, the device
alarm activates. If No, the device alarm does not
activate.
CYBERSENTRY SETTINGS THROUGH THE FRONT PANEL
PATH: SETTINGS
PRODUCT SETUP
 SECURITY
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Login: This setting is applicable for Device Authentication only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the "Supervisor Role" setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. Passwords must obey the
requirements specified the Password Requirements section in chapter 8.The UR device supports five roles. All roles have
their corresponding passwords. The Observer role is the only role that does not require a password.
The roles are defined as follows:
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
Supervisor: This is only an approving role. This role's authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
GE Multilin
SECURITY
LOGIN:
None
 CHANGE LOCAL
 PASSWORDS
 SESSION
 SETTINGS
 RESTORE DEFAULTS
 SUPERVISORY
SYSLOG IP ADDRESS:
0.0.0.0
SYSLOG PORT NUMBER:
514
C70 Capacitor Bank Protection and Control System
MIN
MAX
DEFAULT UNITS
0
99
3
(disabled)
No
Yes
Yes
No
Yes
Yes
Range: Administrator, Engineer, Supervisor,
Operator, Factory (for factory use only), None
See page 5–20.
See page 5–20.
See page 5–20.
See page 5–21.
Range: 0.0.0.0, 255.255.255.255
Range: 1 to 65535
5.2 PRODUCT SETUP
MINIMUM
PERMISSIONS
-
Administrator
-
Administrator
-
Supervisor
(Administrator if
Supervisor has
been disabled)