Table B–9: MODBUS MEMORY MAP (Sheet 32 of 61)
ADDR
REGISTER NAME
7B84
User Programmable Pushbutton 1 Autoreset Delay
7B85
User Programmable Pushbutton 1 Autoreset Function
7B86
User Programmable Pushbutton 1 Local Lock
7B88
User Programmable Pushbutton 1 Message Priority
7B89
User Programmable Pushbutton 1 Remote Lock
7B8B
User Programmable Pushbutton 1 Reset
7B8D
User Programmable Pushbutton 1 Set
7B8F
User Programmable Pushbutton 1 Hold
7B90
...Repeated for User Programmable Pushbutton 2
7BC0
...Repeated for User Programmable Pushbutton 3
7BF0
...Repeated for User Programmable Pushbutton 4
7C20
...Repeated for User Programmable Pushbutton 5
7C50
...Repeated for User Programmable Pushbutton 6
7C80
...Repeated for User Programmable Pushbutton 7
7CB0
...Repeated for User Programmable Pushbutton 8
7DE0
...Repeated for User Programmable Pushbutton 9
7D10
...Repeated for User Programmable Pushbutton 10
7D40
...Repeated for User Programmable Pushbutton 11
7D70
...Repeated for User Programmable Pushbutton 12
7DA0
...Repeated for User Programmable Pushbutton 13
7DD0
...Repeated for User Programmable Pushbutton 14
7E00
...Repeated for User Programmable Pushbutton 15
7E30
...Repeated for User Programmable Pushbutton 16
Neutral Overvoltage (Read/Write Grouped Setting) (3 modules)
7F00
Neutral Overvoltage 1 Function
7F01
Neutral Overvoltage 1 Signal Source
7F02
Neutral Overvoltage 1 Pickup
7F03
Neutral Overvoltage 1 Pickup Delay
7F04
Neutral Overvoltage 1 Reset Delay
7F05
Neutral Overvoltage 1 Block
7F07
Neutral Overvoltage 1 Target
7F08
Neutral Overvoltage 1 Events
7F09
Neutral Overvoltage 1 Curves
7F0A
Reserved (8 items)
7F11
...Repeated for Neutral Overvoltage 2
7F22
...Repeated for Neutral Overvoltage 3
Auxiliary Overvoltage (Read/Write Grouped Setting) (3 modules)
7FA0
Auxiliary Overvoltage 1 Function
7FA1
Auxiliary Overvoltage 1 Signal Source
7FA2
Auxiliary Overvoltage 1 Pickup
7FA3
Auxiliary Overvoltage 1 Pickup Delay
7FA4
Auxiliary Overvoltage 1 Reset Delay
7FA5
Auxiliary Overvoltage 1 Block
7FA7
Auxiliary Overvoltage 1 Target
7FA8
Auxiliary Overvoltage 1 Events
7FA9
Reserved (8 items)
7FB1
...Repeated for Auxiliary Overvoltage 2
7FC2
...Repeated for Auxiliary Overvoltage 3
Frequency (Read Only)
8000
Tracking Frequency
Temp Monitor Actual Values (Read Only Non-Volatile)
81C0
Reserved Register T1
81C1
Reserved Register T2
GE Multilin
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 600
s
0.05
0 to 1
---
1
---
1
0 to 2
---
1
---
1
---
1
---
1
0 to 10
s
0.1
0 to 1
---
1
0 to 5
---
1
0 to 3.00
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 3
---
1
0 to 65535
---
1
0 to 1
---
1
0 to 5
---
1
0 to 3
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 65535
---
1
---
Hz
---
-55 to 125
C
1
-55 to 125
C
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F001
0
F102
0 (Disabled)
F300
0
F220
0 (Disabled)
F300
0
F300
0
F300
0
F001
1
F102
0 (Disabled)
F167
0 (SRC 1)
F001
300
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F116
0 (Definite Time)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
300
F001
100
F001
100
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F001
0
F002
-55
F002
125
B-39
B