5.7 CONTROL ELEMENTS
SETTINGS
CAP 1 CTRL FUNCTION
Enabled = 1
SETTINGS
CAP 1 SET REMOTE 1
OFF = 0
CAP 1 SET REMOTE 2
OFF = 0
CAP 1 SET LOCAL 1
OFF = 0
CAP 1 SET LOCAL 2
OFF = 0
SETTINGS
CAP 1 RMT CTRL EN
OFF = 0
CAP 1 LCL CTRL EN
OFF = 0
SETTINGS
CAP 1 RMT SET AUTO
OFF = 0
CAP 1 LCL SET AUTO
OFF = 0
CAP 1 RMT SET MAN
OFF = 0
CAP 1 LCL SET MAN
OFF = 0
SETTINGS
CAP 1 SWITCH TO MANUAL
ON TRIP:
Yes = 1
SETTINGS
CAP 1 TRIP 1
OFF = 0
CAP 1 TRIP 2
OFF = 0
CAP 1 TRIP 3
5
OFF = 0
CAP 1 TRIP 4
OFF = 0
CAP 1 TRIP 5
OFF = 0
CAP 1 TRIP 6
OFF = 0
SETTINGS
CAP 1 AUTO CTRL EN
OFF = 0
CAP 1 MAN CTRL EN
OFF = 0
SETTINGS
CAP 1 REMOTE OPEN
OFF = 0
CAP 1 LOCAL OPEN
OFF = 0
CAP 1 AUTO OPEN
OFF = 0
SETTINGS
CAP 1 TRIP SEAL-IN DELAY
t
PKP
SETTINGS
CAP 1 BKR OPEN 52b
OFF = 0
CAP 1 BKR CLSD 52a
OFF = 0
SETTINGS
CAP 1 BKR CLOSE BLK
OFF = 0
SETTINGS
CAP 1 REMOTE CLOSE
OFF = 0
CAP 1 LOCAL CLOSE
OFF = 0
CAP 1 AUTO CLOSE
OFF = 0
SETTINGS
CAP 1 CLOSE SEAL-IN DELAY
t
PKP
5-210
OR
S
R
OR
Reset Dominant
Non-Volatile Latch
AND
OR
AND
S
R
AND
Reset Dominant
OR
Non-Volatile Latch
AND
AND
OR
AND
OR
AND
AND
AND
0
OR
AND
AND
OR
AND
AND
0
Figure 5–96: CAPACITOR BANK CONTROL SCHEME LOGIC
C70 Capacitor Bank Protection and Control System
AND
SETTINGS
CAP 1 DISCHARGE TIME:
0
t
DPO
Reset
SETTING
CAP 1 1 CLS OVERRIDE:
OR
Off = 0
AND
OR
AND
5 SETTINGS
FLEXLOGIC OPERAND
CAP 1 IN REMOTE
CAP 1 IN LOCAL
FLEXLOGIC OPERAND
CAP 1 IN AUTO
CAP 1 IN MAN
FLEXLOGIC OPERAND
CAP 1 BKR TRIP
FLEXLOGIC OPERAND
CAP 1 DISCHARGING
FLEXANALOG
CAP 1 DISCHRG TIME
seconds remaining till
closing is enabled
FLEXLOGIC OPERAND
AND
CAP 1 BKR CLOSE
834740A1.DWG