B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 27 of 61)
ADDR
REGISTER NAME
5C08
Neutral Instantaneous Overcurrent 1 Events
5C09
Reserved (8 items)
5C11
...Repeated for Neutral Instantaneous Overcurrent 2
5C22
...Repeated for Neutral Instantaneous Overcurrent 3
5C33
...Repeated for Neutral Instantaneous Overcurrent 4
5C44
...Repeated for Neutral Instantaneous Overcurrent 5
5C55
...Repeated for Neutral Instantaneous Overcurrent 6
5C66
...Repeated for Neutral Instantaneous Overcurrent 7
5C77
...Repeated for Neutral Instantaneous Overcurrent 8
5C88
...Repeated for Neutral Instantaneous Overcurrent 9
B
5C99
...Repeated for Neutral Instantaneous Overcurrent 10
5CAA
...Repeated for Neutral Instantaneous Overcurrent 11
5CBB
...Repeated for Neutral Instantaneous Overcurrent 12
Ground Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5D00
Ground Time Overcurrent 1 Function
5D01
Ground Time Overcurrent 1 Signal Source
5D02
Ground Time Overcurrent 1 Input
5D03
Ground Time Overcurrent 1 Pickup
5D04
Ground Time Overcurrent 1 Curve
5D05
Ground Time Overcurrent 1 Multiplier
5D06
Ground Time Overcurrent 1 Reset
5D07
Ground Time Overcurrent 1 Block
5D09
Ground Time Overcurrent 1 Target
5D0A
Ground Time Overcurrent 1 Events
5D0B
Reserved (6 items)
5D11
...Repeated for Ground Time Overcurrent 2
5D22
...Repeated for Ground Time Overcurrent 3
5D33
...Repeated for Ground Time Overcurrent 4
5D44
...Repeated for Ground Time Overcurrent 5
5D55
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5DA0
Ground Instantaneous Overcurrent 1 Function
5DA1
Ground Instantaneous Overcurrent 1 Signal Source
5DA2
Ground Instantaneous Overcurrent 1 Pickup
5DA3
Ground Instantaneous Overcurrent 1 Delay
5DA4
Ground Instantaneous Overcurrent 1 Reset Delay
5DA5
Ground Instantaneous Overcurrent 1 Block
5DA7
Ground Instantaneous Overcurrent 1 Target
5DA8
Ground Instantaneous Overcurrent 1 Events
5DA9
Reserved (8 items)
5DB1
...Repeated for Ground Instantaneous Overcurrent 2
5DC2
...Repeated for Ground Instantaneous Overcurrent 3
5DD3
...Repeated for Ground Instantaneous Overcurrent 4
5DE4
...Repeated for Ground Instantaneous Overcurrent 5
5DF5
...Repeated for Ground Instantaneous Overcurrent 6
5E06
...Repeated for Ground Instantaneous Overcurrent 7
5E17
...Repeated for Ground Instantaneous Overcurrent 8
5E28
...Repeated for Ground Instantaneous Overcurrent 9
5E39
...Repeated for Ground Instantaneous Overcurrent 10
5E4A
...Repeated for Ground Instantaneous Overcurrent 11
5E5B
...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
B-34
0 to 4294967295
0 to 4294967295
0 to 4294967295
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 1
---
1
0 to 30
pu
0.001
0 to 16
---
1
0 to 600
---
0.01
0 to 1
---
1
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
0 to 30
pu
0.001
0 to 600
s
0.01
0 to 600
s
0.01
---
1
0 to 2
---
1
0 to 1
---
1
0 to 1
---
1
0 to 5
---
1
---
1
APPENDIX B
FORMAT
DEFAULT
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F122
0 (Phasor)
F001
1000
F103
0 (IEEE Mod Inv)
F001
100
F104
0 (Instantaneous)
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F102
0 (Disabled)
F167
0 (SRC 1)
F001
1000
F001
0
F001
0
F300
0
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F001
0
F300
0
GE Multilin

Advertisement

Table of Contents
loading