GE C70 Instruction Manual page 288

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
5
e) NEUTRAL CURRENT UNBALANCE (ANSI 60NU, IEC PVCB/PTOC)

PATH: SETTINGS
GROUPED...
 NEUTRAL CURRENT
 UNBALANCE 1
5-164
Figure 5–68: NEUTRAL DIRECTIONAL OVERCURRENT LOGIC
SETTING GROUP 1(6)
NTRL CUR UNBALCE 1
FUNCTION: Disabled
NTRL CUR UNBALCE 1
MESSAGE
BANK SOURCE: SRC 1
NTRL CUR UNBALCE 1
MESSAGE
K MAG: 0.0000
NTRL CUR UNBALCE 1
MESSAGE
K ANG: 0°
NTRL CUR UNBALCE 1
MESSAGE
STG 1 PKP: 0.020 pu
NTRL CUR UNBALCE 1
MESSAGE
STG 1 SLOPE: 2.0%
C70 Capacitor Bank Protection and Control System


NEUTRAL CURRENT
NEUTRAL CURRENT UNBALANCE 1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.0000 to 0.1500 in steps of 0.0001
Range: 0 to 359° in steps of 1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1
5 SETTINGS
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents