E.1.1 Dnp V3.00 Device Profile - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

APPENDIX E
APPENDIX E DNP COMMUNICATIONSE.1DEVICE PROFILE DOCUMENT
The following table provides a 'Device Profile Document' in the standard format defined in the DNP 3.0 Subset Definitions
Document.
Table E–1: DNP V3.00 DEVICE PROFILE (Sheet 1 of 3)
(Also see the IMPLEMENTATION TABLE in the following section)
Vendor Name: General Electric Multilin
Device Name: UR Series Relay
Highest DNP Level Supported:
For Requests:
Level 2
For Responses: Level 2
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete
list is described in the attached table):
Binary Inputs (Object 1)
Binary Input Changes (Object 2)
Binary Outputs (Object 10)
Control Relay Output Block (Object 12)
Binary Counters (Object 20)
Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)
Analog Inputs (Object 30)
Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
File Transfer (Object 70)
Internal Indications (Object 80)
Maximum Data Link Frame Size (octets):
Transmitted: 292
Received:
292
Maximum Data Link Re-tries:
 None
 Fixed at 3
 Configurable
Requires Data Link Layer Confirmation:
 Never
 Always
 Sometimes
 Configurable
GE Multilin
Device Function:
 Master
 Slave
Maximum Application Fragment Size (octets):
Transmitted: configurable up to 2048
Received:
Maximum Application Layer Re-tries:
 None
 Configurable
C70 Capacitor Bank Protection and Control System
E.1 DEVICE PROFILE DOCUMENT

E.1.1 DNP V3.00 DEVICE PROFILE

2048
E
E-1