GE C70 Instruction Manual page 507

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 4 of 61)
ADDR
REGISTER NAME
1608
Field latching output close operand states
1609
Field latching output open driver states
160A
Field latching output close driver states
160B
Field latching output physical states
160C
Field unit online/offline states
160D
Fiedl RTD input trouble states
160E
Field transducer input trouble states
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet primary fibre channel status
1611
Ethernet secondary fibre channel status
1612
Ethernet tertiary fibre channel status
Data Logger Actuals (Read Only)
1618
Data logger channel count
1619
Time of oldest available samples
161B
Time of newest available samples
161D
Data logger duration
Field Unit RTD Actuals (Read Only) (8 modules)
16C0
Field RTD x Value
16C1
...Repeated for module number 2
16C2
...Repeated for module number 3
16C3
...Repeated for module number 4
16C4
...Repeated for module number 5
16C5
...Repeated for module number 6
16C6
...Repeated for module number 7
16C7
...Repeated for module number 8
Field Unit Transducer Actuals (Read Only) (8 modules)
16C8
Field Transducer x Value
16CA
...Repeated for module number 2
16CC
...Repeated for module number 3
16CE
...Repeated for module number 4
16D0
...Repeated for module number 5
16D2
...Repeated for module number 6
16D4
...Repeated for module number 7
16D6
...Repeated for module number 8
Source Current (Read Only) (6 modules)
1800
Source 1 Phase A Current RMS
1802
Source 1 Phase B Current RMS
1804
Source 1 Phase C Current RMS
1806
Source 1 Neutral Current RMS
1808
Source 1 Phase A Current Magnitude
180A
Source 1 Phase A Current Angle
180B
Source 1 Phase B Current Magnitude
180D
Source 1 Phase B Current Angle
180E
Source 1 Phase C Current Magnitude
1810
Source 1 Phase C Current Angle
1811
Source 1 Neutral Current Magnitude
1813
Source 1 Neutral Current Angle
1814
Source 1 Ground Current RMS
1816
Source 1 Ground Current Magnitude
1818
Source 1 Ground Current Angle
1819
Source 1 Zero Sequence Current Magnitude
181B
Source 1 Zero Sequence Current Angle
181C
Source 1 Positive Sequence Current Magnitude
181E
Source 1 Positive Sequence Current Angle
GE Multilin
0 to 4294967295
0 to 4294967295
-32768 to 32767
-32.768 to 32.767
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
0 to 999999.999
-359.9 to 0
C70 Capacitor Bank Protection and Control System
RANGE
UNITS
STEP
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 65535
---
1
0 to 2
---
1
0 to 2
---
1
0 to 2
---
1
0 to 16
channel
1
seconds
1
seconds
1
0 to 999.9
days
0.1
°C
1
---
0.001
A
0.001
A
0.001
A
0.001
A
0.001
A
0.001
degrees
0.1
A
0.001
degrees
0.1
A
0.001
degrees
0.1
A
0.001
degrees
0.1
A
0.001
A
0.001
degrees
0.1
A
0.001
degrees
0.1
A
0.001
degrees
0.1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F500
0
F500
0
F500
0
F500
0
F500
0
F500
0
F500
0
F134
0 (Fail)
F134
0 (Fail)
F134
0 (Fail)
F001
0
F050
0
F050
0
F001
0
F002
0
F004
0
F060
0
F060
0
F060
0
F060
0
F060
0
F002
0
F060
0
F002
0
F060
0
F002
0
F060
0
F002
0
F060
0
F060
0
F002
0
F060
0
F002
0
F060
0
F002
0
B-11
B