Leds Of The Repeater Module - Procentec ComBricks User Manual

Profibus data hub for repeaters and fiber optics modules
Table of Contents

Advertisement

7.11 LEDs of the repeater module

The LEDs on the repeater modules are very useful for visual diagnostics.
Table 5 - LEDs on the standard repeater module
RDY
Repeater module has
NOT been configured yet.
RX
NO valid telegrams
detected on this channel.
ER
The baudrate has
been detected.
SW
Internal termination for
this channel is OFF.
Table 6 - Additional LEDs on the SCOPE repeater module
MIN
Valid telegram signal
amplitude (> 2.5 V)
TERM
Valid idle voltage
(~ 1 V).
HWE
Repeater is
operational.
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
OFF
Head Station is
configuring the repeater
module.
1 or more devices are
communicating on this
channel.
Problem in the
cabling has been detected
on this channel.
OFF
Blinking
Repeater module has
been configured and is
operational
1 or more devices are
communicating on this
channel.
This channel has not
detected the baudrate (yet)
or there is a problem with
the wiring of the cable.
Internal termination for
this channel has been
activated.
Blinking
Telegram signal
amplitude is too low
(< 2.5 V)
Idle voltage is too low
(< 1 V)
Internal repeater
error (contact PROCENTEC)
ON
ON
90/219