11.1.1 RDY LED

The RDY LED indicates power supply and connection with the Head Station. Also a firmware update is indicated
with this LED.
LED
State
Meaning
RDY
Off
No power supply, or PBS-001 module is faulty.
(green)
There is no voltage at the module, or the module has a hardware defect.
Remedy: Connect the 24 V DC supply voltage at the Head station.
Flashing
The PBS-001 module is connecting with the Head Station. This state is allowed for a
(1 Hz)
short time (max 1 minute).
Flashing
A backplane firmware update of the PBS-001 module is executed by the Head
(0.3Hz)
Station (max 1 minute).
On
The connection with the Head Station is established.

11.1.2 PROFIBUS LEDs

The PBS-001 module has three PROFIBUS diagnostic LEDs: RUN, SF (System Fail) and BF (Bus Fail).
LED
State
Meaning
RUN
Off
Internal application firmware is not running (PROFIBUS stack).
(green)
Remedy: Update application firmware.
On
Internal application firmware is running (PROFIBUS stack).
SF
Off
No error
System
Fail
(red)
On
System error, or the received expected configuration (from configuration tool) does
not match the actual configuration (I/O modules in the backplane, or gateway has a
problem).
BF
Off
PBS-001 module is in Data Exchange with a PROFIBUS master.
(red)
On
PBS-001 module is not in Data Exchange with a PROFIBUS master.

11.1.3 Dipswitches

The PBS-001 has four dipswitches, located on the bottom
ComBricks User Manual v6.4.0 | January 18| © PROCENTEC
107/219